Do not use an extension cord or adapter plug with this water heater.
The water heater must be electrically grounded in accordance with local codes and ordinances
or, in the absence of local codes, in accordance with the National Electrical Code, ANSI/ NFPA
No. 70.
This water heater is equipped with a three-prong (grounding) plug for your protection
against shock hazard and should be plugged directly into a properly grounded three-prong
receptacle. Do not cut or remove the grounding terminal from this plug.
When connecting the power supply, follow these guidelines:
Do not rely on the gas or water piping to ground the water heater. Ground locations are provided
inside the water heater.
The water heater requires 120 VAC, 60 Hz power from a properly grounded circuit.
If using the 6.5 ft (2.0 m) power cord supplied with the water heater, plug the power cord into a
standard 3 prong 120 VAC, 60 Hz properly grounded wall outlet. The supplied power cord is
outdoor rated and can be used for outdoor installations.
A disconnect switch may be required and installed for the incoming 120 VAC power for outdoor
installation. The switch should be a type that is suitable for outdoor use. Check the National
Electrical Code, ANSI/NFPA 70 and your local codes for a proper switch type to use in your area.
Power connections must be protected from the weather.