User manual

31/85 V 1.0
48 Setting-up Swing pro Series
48.1 DC-Wiring
Position of the switch on the front panel must be OFF.
A high power fuse must be installed direct to the battery to protect the DC-Wiring (not for Swing pro 200-12-230).
DC – current according to the datasheet.
Not installing a fuse may result in melting or even burning DC-Cables in case of excessive overload or failure of
the inverter.
The way of wiring has influence on the EMC behaviour of the system. Most problems using inverter are because
of unprofessional wiring. Lay the cables in a metal duct. If this is not possible the cables should be twisted and lay
parallel to a metal bar.
To thin cable or loose connections can cause dangerous overheating of cables or terminals. Always use DC
cables of the correct size to avoid fire and other damage.
Use DC Cable with appropriate size and cable lug (see picture).
Only SWING pro 200-12-230
DC-Connector already mounted to DC-Cable. Do not remove. It is for use with cigarette lighter output
in your car. Check the fuse of your car for correct size (>15A).
Connect the cables with care to the battery/inline fuse. If possible use coloured cables. Red colour means battery
positive, while black is used for battery negative. Reversing positive and negative will cause major damage to the
inverter and is not covered by warranty.
Note: Large capacitors in the units may hold DC-Voltage for a long period of time. Also a spark may occur while
connecting the DC-cables or inserting the DC-Fuse after installation. This is normal.
If you connect other consumers to the battery contact your dealer.
48.2 AC-Wiring
Use the included AC-Connector to connect the AC-Load to the output of the inverter.
Even the inverter is protected against overload and short circuit, we recommend to use an AC-Circuit breaker of
correct size.
For safe operation it is necessary to connect earth (PE) and neutral (N) of the inverter output to central ground of
the inverter.
Even more safe is to use a 15mA or 30mA earth leakage switch in the AC-Installation.
48.3 Grounding
The earth wire protection is only possible if the inverter enclosure is also connected to earth. Use a . 8-10mm2
cable (AWG 8) and connect it to the earth terminal of the inverter. This is also important for lighting protection.