User manual

37/85 V 1.0
57.7 Over voltage protection indicator: (OVP)
The over voltage indicator indicates that the power inverter has shut itself down because its input voltage
exceeded the maximum input voltage.
57.8 Under voltage protection indicator: (UVP)
The under voltage indicator indicates that the power inverter has shut itself down because its input voltage fell
below minimum input voltage.
57.9 Over temp protection indicator: (OTP)
The over temp indicator indicates that the power inverter has shut itself down because its temp has become
overheated. The power inverter may overheat because it has been operated at power levels above its rating, or
because it has been installed in a location which does not allow it to dissipate heat properly. The power inverter
will automatically back up, once it has cooled off.
57.10 Overload protection indicator: (OLP)
The overload indicator indicates that the power inverter has shut down. A manual reset is necessary (switch it
OFF and ON again) to restart operation. This is a safety function to protect your battery when the inverter
operates in a remote area.
Model
DC Input over
voltage shutdown
DC Input over
voltage alarm
DC Input under
voltage alarm
DC Input under
voltage shutdown
JAZZ pro 700 12V
JAZZ pro 1000 12V
16.0 VDC 15.5 VDC 10.5 VDC 10.0 VDC
JAZZ pro 700 24V
JAZZ pro 1000 24V
32.0 VDC 31.0 VDC 21.0 VDC 20.0 VDC
JAZZ pro 700 48V
JAZZ pro 1000 48V
62.0 VDC 61.0 VDC 43.0 VDC 42.0 VDC