User manual

41/85 V 1.0
61 Configure the inverter prior to operation
61.1 Frequency setting
The AC-Frequency may be selected by DIP-Switch S4 on the front panel as follows.
AC-Frequency (Hz) S1
50 0
60 I
To activate the new selected value, the inverter must be turned ON and OFF (Reset) .
61.2 Sleep mode/ Power saving mode (automatic load detection)
Power Saving Mode S4
enable 0
disable I
To activate the new selected value, the inverter must be turned ON and OFF (Reset) .
61.3 Optional PC RS 232 connection
Baud Rate S2 S3
2400 I I
4800 0 I
9600 I 0
19200 0 0
To activate the new selected value, the inverter must be turned ON and OFF (Reset) .
Caution! If the inverter is detecting a load it takes 15 to 18 seconds before the output power is available (delayed).
Be careful when working with machinery (we recommend to disable the sleep mode).
61.4 Output Voltage Tune ACV-ADJ
Tune VR ( VAC ) output voltage from 100 – 120 VAC or 200 – 240 VAC
The VAC value will gradually increase, tune VR from right to left.
62 Operation
The Inverter is controlled by an ON / OFF switch located on the front panel of the inverter.
Engaging
Set the power switch to the ON position; you will hear three beep. After that, you will hear the continuous sound
from internal alarm. Then, the AC voltage shows on the display. The Inverter is ready to use.
Power down
Switch to „OFF-Position“. All LED’s are dark. The inverter output is OFF.
Remark
Even if the inverter is switched to off, it is not disconnected from the battery. It still draws very little power from the
battery. If you don’t need the inverter for an extended period disconnect it from the battery to avoid low discharge
of battery.