10. SPECIFICATIONS
CC-Link communication
Protocol: CC-Link Ver. 2.00/Ver. 1.10
Communication speed: 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps
Communication distance: Refer to table shown below
Communication speed Maximum network length
10 Mbps 100 m
5 Mbps 200 m
2.5 Mbps 400 m
625 kbps 900 m
156 kbps 1200 m
Station number: 1 to 61 (4 stations occupied 1 time, 4 stations occupied 2 times)
1 to 64 (1 station occupied 1 time)
Connection cable: CC-Link dedicated cable Ver. 1.10 (Shielded twisted pair wire)
Number of occupied station/extended cyclic and CC-Link version:
CC-Link Ver. 1.10: 1 station occupied 1 time, 4 stations occupied 1 time
CC-Link Ver. 2.00: 4 stations occupied 2 times
Connection method: Terminals
Termination resistor: External installation is necessary
(Between the DA and DB terminals: 110 Ω 1/2 W)
Communication data length:
Refer to table shown below
Number of Occupied
station/Extended cyclic
Remote
Input/Output
(RX/RY)
Remote
register
(RWr/RWw)
Number of
Controller
connection
4 stations occupied 1 time
Input: 128-
b
it
Output: 128-bit
RWr: 16-wor
d
RWw: 16-word
8 controllers o
r
16 controllers
4 stations occupied 2 times
Input: 224-
b
it
Output: 224-bit
RWr: 32-wor
d
RWw: 32-word
16 controllers o
r
32 controllers
1 station occupied 1 time
Input: 32-
b
it
Output: 32-bit
RWr: 4-wor
d
RWw: 4-word
1 controller o
r
2 controllers
Controller communication
Interface: Base on RS-485, EIA standard (Multi-drop connection is available.)
Protocol: Modbus-RTU
Synchronous method: Half-duplex start-stop synchronous type
Communication method: 2-wire system, half-duplex multi-drop connection
Communication speed: 9600 bps, 19200 bps, 38400 bps
Data bit configuration: Data 8-bit, Without parity bit, Stop 1-bit
Maximum connections: 31 controllers (FB100/400/900) [Device address setting: 1 to 99]
Connection method: Terminals
Termination resistor: Built-in terminal base of COM-JC
[ON/OFF select with switch (120 Ω 1/2 W)]