Instruction manual

5. SETTING
IMR01Y06-E6
18
5.3 Occupied Station/Extended Cyclic and Controller
Communication Speed Setting
The DIP switch at the left side of the mainframe sets the occupied station/extended cyclic and
controller communication speed.
Left side view
DIP switch
12345678
ON
12345678
ON
OFF
1 2 Controller communication speed
OFF OFF
38400 bps
ON OFF
9600 bps
OFF ON
19200 bps
ON ON
38400 bps
Factory set value: 19200 bps
3 4 5 Number of Occupied station/Extended cyclic
OFF
OFF OFF
4 stations occupied 1 time (8 controllers assignment)
ON
OFF OFF
4 stations occupied 1 time (16 controllers assignment)
OFF
ON
OFF
4 stations occupied 2 times (16 controllers assignment)
ON ON
OFF
4 stations occupied 2 times (31 controllers assignment)
OFF OFF
ON 1 station occupied 1 time (1 controller assignment)
ON
OFF
ON 1 station occupied 1 time (2 controllers assignment)
OFF ON ON
Do not set this one
ON ON ON
Factory set value: 4 stations occupied 1 time (8 controllers assignment)
CC-Link version varies according to the specification of Occupied station/Extended
cyclic of the COM-JC. Select CC-Link version of PLC by setting the following
CC-Link specifications:
1 station occupied 1 time/4 stations occupied 1 time: CC-Link Ver. 1.10
4 stations occupied 2 times: CC-Link Ver. 2.00
6 7 8
OFF OFF OFF
Fixed