Instruction manual

5. SETTING
IMR01Y06-E6
19
5.4 Controller Setting
[Controller communication conditions: Use communication 1 side]
Device address: 1 to 99 (Zero is not settable)
The device address numbers must be continuous starting from 1.
Communication protocol: Modbus-RTU
Communication speed: 9600 bps, 19200 bps, 38400 bps
Match the communication speed of the FB series controller to that
of the COM-JC. The communication speed of the COM-JC can be
adjusted with a DIP switch. (Refer to page 18)
Data bit configuration: Data 8-bit, Without parity bit, Stop 1-bit
For setting procedure, refer to FB100 Communication Quick Manual (IMR01W15-E),
FB400/FB900 Communication Quick Manual (IMR01W07-E) or FB100/FB400/FB900
Communication Instruction Manual (IMR01W04-E).