Instruction manual

6. CC-Link COMMUNICATION
IMR01Y06-E6
24
Extension number for setting selection processing
The content of the extended setting remote register is selected and the set value is changed.
After the Extension number for setting [RYn6 to RYnB] is set, turn on the Extended setting flag
(Setting update flag) [RYnD]. After the content of the Remote register [RWwn to RWwn+3] is set,
check that Extended setting completion [RXnD] is turned on and then turn off the Extended setting
flag (Setting update flag) [RYnD]. If the Extended setting flag (Setting update flag) [RYnD] is turned
off, the Extended setting completion [RXnD] is turned off.
Extension numbe
r
for setting
[RYn6 to RYnB]
Extended setting flag
(Setting update flag)
[RYnD]
Extended setting
completion
[RXnD]
Remote register
[RWwn to RWwn+3]
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Data usage Data usage
Regardless of the number of Occupied station and the Extended cyclic, the above processing
is also necessary if the Set value (SV) assigned to the Remote register (RWw) as a fixed
value is changed.
AT start procedure
Instructs AT execution.
Remote re
g
ister [RWwn]
(Extension number 4:
PID/AT transfer)
Extended setting flag
(Setting update flag)
[RYnD]
Extended setting
completion
[RXnD]
A
T setting status
PID/AT transfer status
[RXn4]
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Data = 1
Data = 0