Instruction manual
7. COMMUNICATION DATA LIST
IMR01Y06-E6
27
7.1.1 1 station occupied 1 time
Remote input
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 32-bit
Address Communication item Data range
Factory
set value
RXn0 Device address 1 Event 1 state
0: OFF
1: ON
⎯
RXn1 Event 2 state
⎯
RXn2 Burnout state
0: OFF
1: ON
⎯
RXn3 Heater break alarm
(HBA) state
0: OFF
1: ON
⎯
RXn4 PID/AT transfer
0: PID control
1: Autotuning (AT)
⎯
RXn5 Device address 2 Event 1 state
0: OFF
1: ON
⎯
RXn6 Event 2 state
⎯
RXn7 Burnout state
0: OFF
1: ON
⎯
RXn8 Heater break alarm
(HBA) state
0: OFF
1: ON
⎯
RXn9 PID/AT transfer
0: PID control
1: Autotuning (AT)
⎯
RXnA Unused
⎯
⎯
RXnB
RXnC Extended display completion
0: OFF
1: ON
⎯
RXnD Extended setting completion
⎯
RXnE Unused
⎯
⎯
RXnF Hardware error flag
0: OFF
1: ON
Hardware error flag ON condition
• Hardware error
• RAM read/write error
• Stack overflow
• Memory backup error
• Configuration error
⎯
RX(n+1)0 Reserved
⎯
⎯
y
y
y
RX(n+1)7
RX(n+1)8 Initialize data processing request flag
0: OFF
1: ON
⎯
RX(n+1)9 Initialize data setting completion flag
0: OFF
1: ON
⎯
RX(n+1)A Error status flag
0: OFF
1: ON
Error status flag ON condition
• Communication error
⎯
RX(n+1)B Remote ready
0: Not ready state
1: Ready state
⎯
RX(n+1)C Reserved
⎯
⎯
y
y
y
RX(n+1)F