7. COMMUNICATION DATA LIST
IMR01Y06-E6
29
7.1.2 4 stations occupied 1 time
Remote input
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 128-bit
Address Communication item Data range
Factory
set value
RXn0 Device address 1
Event 1 state
0: OFF
1: ON
⎯
RXn1
Event 2 state
⎯
RXn2
Burnout state
0: OFF
1: ON
⎯
RXn3
Heater break alarm
(HBA) state
0: OFF
1: ON
⎯
RXn4
PID/AT transfer
0: PID control
1: Autotuning (AT)
⎯
RXn5 Device address 2
Event 1 state
0: OFF
1: ON
⎯
RXn6
Event 2 state
⎯
RXn7
Burnout state
0: OFF
1: ON
⎯
RXn8
Heater break alarm
(HBA) state
0: OFF
1: ON
⎯
RXn9
PID/AT transfer
0: PID control
1: Autotuning (AT)
⎯
RXnA
Unused
⎯
⎯
RXnB
RXnC
Extended display completion
0: OFF
1: ON
⎯
RXnD
Extended setting completion
0: OFF
1: ON
⎯
RXnE Unused
⎯
⎯
RXnF Hardware error flag
0: OFF
1: ON
Hardware error flag ON condition
• Hardware error
• RAM read/write error
• Stack overflow
• Memory backup error
• Configuration error
⎯
RX(n+1)0 Unused
⎯
⎯
y
y
y
RX(n+1)F
RX(n+2)0 Device address 3
Event 1 state
0: OFF
1: ON
⎯
RX(n+2)1
Event 2 state
⎯
RX(n+2)2
Burnout state
0: OFF
1: ON
⎯
RX(n+2)3
Heater break alarm
(HBA) state
0: OFF
1: ON
⎯
RX(n+2)4
PID/AT transfer
0: PID control
1: Autotuning (AT)
⎯
Continued on the next page.