Instruction manual

7. COMMUNICATION DATA LIST
IMR01Y06-E6
48
7.2.3 4 stations occupied 1 time (8 controllers assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) Master station (PLC)
Data capacity: 16-word
Address Communication item Data range
Factory
set value
RWrn Device address 1 Measured value (PV) Input scale low to
Input scale high
RWrn+1 Device address 2 Measured value (PV)
RWrn+2 Device address 3 Measured value (PV)
RWrn+3 Device address 4 Measured value (PV)
RWrn+4 Device address 5 Measured value (PV)
RWrn+5 Device address 6 Measured value (PV)
RWrn+6 Device address 7 Measured value (PV)
RWrn+7 Device address 8 Measured value (PV)
RWrn+8 Device address 1 For extended area display
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5
and from RY(n+1)0 to
RY(n+1)2.
RWrn+9 Device address 2 For extended area display
RWrn+A Device address 3 For extended area display
RWrn+B Device address 4 For extended area display
RWrn+C Device address 5 For extended area display
RWrn+D Device address 6 For extended area display
RWrn+E Device address 7 For extended area display
RWrn+F Device address 8 For extended area display
Remote register (RWw)
Data direction: Master station (PLC) COM-JC (Remote device station)
Data capacity: 16-word
Address Communication item Data range
Factory
set value
RWwn Device address 1 Set value (SV) Setting limiter low to
Setting limiter high
0
RWwn+1
Device address 2 Set value (SV) 0
RWwn+2
Device address 3 Set value (SV) 0
RWwn+3
Device address 4 Set value (SV) 0
RWwn+4
Device address 5 Set value (SV) 0
RWwn+5
Device address 6 Set value (SV) 0
RWwn+6
Device address 7 Set value (SV) 0
RWwn+7
Device address 8 Set value (SV) 0
RWwn+8
Device address 1 For extended area setting
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB
and from RY(n+1)8 to
RY(n+1)A.
RWwn+9 Device address 2 For extended area setting
RWwn+A Device address 3 For extended area setting
RWwn+B Device address 4 For extended area setting
RWwn+C Device address 5 For extended area setting
RWwn+D Device address 6 For extended area setting
RWwn+E Device address 7 For extended area setting
RWwn+F Device address 8 For extended area setting
When the Set value (SV) assigned to the Remote register (RWw) as a fixed value is changed,
operation of the extension setting flag (setting update flag) is also necessary. For details,
refer to Extension number for setting selection processing (P. 24).