7. COMMUNICATION DATA LIST
IMR01Y06-E6
55
When write data
z Setting of extension number for setting
Extension number for setting sets it with Remote output RYn6 to RynB and RY(n+1)8 to RY(n+1)A.
Bit image
RY(n+1)A RY(n+1)9 RY(n+1)8 RYnB RYnA RYn9 RYn8 RYn7 RYn6
Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Bit data: 0: OFF 1: ON [Decimal number: 0 to 511]
For the 1 station occupied 1 time setting, setting range of extension number becomes RYn6
to RYnB [Decimal number: 0 to 63].
z Setting of area number for setting
Area number for setting sets it with Remote output RY(n+2)8 to RY(n+2)B.
Bit image
RY(n+2)B RY(n+2)A RY(n+2)9 RY(n+2)8
Bit 3 Bit 2 Bit 1 Bit 0
Bit data: 0: OFF 1: ON [Decimal number: 0 to 16 (0, 9 to 16: Control area)]
For 1 station occupied 1 time setting, cannot do an assignment of area number. Become
communication item of a control area.
[Example] When set extension number for setting to “3: Set value (SV),” and set area number for
setting to “5.”
Number of Occupied station/Extended cyclic setting: 4 stations occupied 1 time
Setting of extension number for setting
Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 0 0 0 1 1
Ð
RY(n+1)A RY(n+1)9 RY(n+1)8 RYnB RYnA RYn9 RYn8 RYn7 RYn6
OFF OFF OFF OFF OFF OFF OFF ON ON
Bit data: 0: OFF 1: ON
Setting of area number for setting
Bit 3 Bit 2 Bit 1 Bit 0
0 1 0 1
Ð
RY(n+2)B RY(n+2)A RY(n+2)9 RY(n+2)8
OFF ON OFF ON
Bit data: 0: OFF 1: ON
Extension number 3:
Set value (SV)
Memory area number 5