7. COMMUNICATION DATA LIST
IMR01Y06-E6
56
Extension number list
Attribute:
RO: Read only data [Remote device station (COM-JC) Master station (PLC)]
R/W: Read and Write data [Remote device station (COM-JC) Master station (PLC)]
: Data related multi-memory area function
Reading data of unused setting items are factory set values. Unused setting items may not be
written. To do so will not cause an error however and data will be rejected.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
0 Measured value (PV) RO Input scale low to Input scale high
Varies with the setting of the Decimal point
position selection.
1
Manipulated output value
(MV1) monitor
[heat-side]
RO
PID control or Heat/Cool PID control:
5.0 to +105.0 %
Position proportioning PID control with
feedback resistance (FBR) input:
0.0 to 100.0 %
2
Current transformer 1 (CT1)
input value monitor
RO
0.0 to 30.0 A (CTL-6-P-N)
0.0 to 100.0 A (CTL-12-S56-10L-N)
3 Set value (SV) R/W Setting limiter low to Setting limiter high
Varies with the setting of the Decimal point
position selection.
TC/RTD:
0, 0.0 or 0.00
V/I: 0.0
4 PID/AT transfer
1
R/W
0: PID control
1: Autotuning (AT) *
* When the Autotuning (AT) is finished, the control
will automatically returns to 0: PID control.
0
5
Proportional band
[heat-side]
R/W
TC/RTD inputs:
0 to Input span, 0.0 to Input span or
0.00 to Input span (Unit: °C [°F])
Varies with the setting of the Decimal point
position selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span
(0, 0.0 or 0.00: ON/OFF action)
TC/RTD:
30, 30.0 or
30.00
V/I: 30.0
6
Integral time
[heat-side]
R/W
PID control or Heat/Cool PID control:
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action)
[both heat-side and cool-side]
Position proportioning PID control:
1 to 3600 seconds or 0.1 to 1999.9 seconds
Varies with the setting of the Integral/Derivative
time decimal point position selection.
240
7
Derivative time
[heat-side]
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the Integral/Derivative
time decimal point position selection.
60
8 PV bias R/W
Input span to
+
Input span
Varies with the setting of the Decimal point
position selection.
0, 0.0 or 0.00
1
For the operation, refer to the 6.2 CC-Link Flag Operation (P. 22).
Continued on the next page.