Instruction manual

7. COMMUNICATION DATA LIST
IMR01Y06-E6
57
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
9 Event 1 set value R/W
Deviation:
Input span to +Input span
Varies with the setting of the Decimal
point position selection.
Process and set value:
Input scale low to Input scale high
Varies with the setting of the Decimal
point position selection.
Manipulated output value (MV1 or MV2):
5.0 to +105.0 %
If the Event type corresponds to “0: None,”
set to RO (Read only data).
50, 50.0 or
50.00
10 Event 2 set value
R/W
50, 50.0 or
50.00
11
Reserved
y
y
y
15
16 Unused
17 RUN/STOP transfer R/W
Logic of RUN/STOP transfer is different by
model code.
For COM-JC01-1
0: RUN (Control start)
1: STOP (Control stop)
For COM-JC01-2
0: STOP (Control stop)
1: RUN (Control start)
0
18 Proportional cycle time
[heat-side]
R/W 0.1 to 100.0 seconds
M: Relay contact output
V: Voltage pulse output
T: Triac output
D: Open collector output
This item becomes RO (Read only data) for
the Voltage/Current output specification.
M: 20.0
V, T, D: 2.0
19 Auto/Manual transfer R/W
0: Auto mode
1: Manual mode
0
20
Manual manipulated output
value
R/W
PID control, Position proportioning PID control
with feedback resistance (FBR) input:
Output limiter low [MV1] to
Output limiter high [MV1]
Heat/Cool PID control:
Output limiter high [MV2] to
+Output limiter high [MV1]
(105.0 to +105.0 %)
0.0
21 Setting limiter high R/W Setting limiter low to Input scale high
Varies with the setting of the Decimal point
position selection.
Input scale
high
22 Setting limiter low R/W Input scale low to Setting limiter high
Varies with the setting of the Decimal point
position selection.
Input scale
low
23 PV digital filter R/W
0.0 to 100.0 seconds
(0.0: Unused)
0.0
Continued on the next page.