7. COMMUNICATION DATA LIST
IMR01Y06-E6
58
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
24
Heater break alarm 1
(HBA1) set value
R/W
0.0 to 30.0 A (CTL-6-P-N)
0.0 to 100.0 A (CTL-12-S56-10L-N)
(0.0: Unused)
If there is no Current transformer 1 (CT1) or
CT1 is assigned to “0: None,” set to RO (Read
only data).
0.0
25 Decimal point position R/W
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC inputs:
K, J, E: Only 0 or 1 can be set.
T, U, L: Only 1 can be set.
Other than the above:
Only 0 can be set.
RTD inputs: From 0 to 2 can be set.
V/I inputs: From 0 to 4 can be set.
Based on
model code.
When not
specifying:
TC/RTD: 0
V/I: 1
26
Manipulated output value
(MV2) monitor
[cool-side]
RO
5.0 to
+
105.0 %
27
Proportional band
[cool-side]
R/W
TC/RTD inputs:
1 to Input span, 0.1 to Input span or
0.01 to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of input span
If control is other than Heat/Cool PID control,
set to RO (Read only data).
TC/RTD:
30, 30.0 or
30.00
V/I: 30.0
28
Proportional cycle time
[cool-side]
R/W
0.1 to 100.0 seconds
M: Relay contact output
V: Voltage pulse output
T: Triac output
D: Open collector output
If control is other than Heat/Cool PID control,
set to RO (Read only data).
This item becomes RO (Read only data) for
the Voltage/Current outputs specification.
M: 20.0
V, T, D: 2.0
29 Overlap/Deadband R/W
TC/RTD inputs:
Input span to +Input span (Unit:°C [°F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
100.0 to +100.0 % of input span
Minus () setting results in Overlap.
However, the overlapping range is within the
proportional range.
If control is other than Heat/Cool PID control,
set to RO (Read only data).
0, 0.0 or 0.00
30 Unused
Continued on the next page.