7. COMMUNICATION DATA LIST
IMR01Y06-E6
59
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
31 Set value (SV) monitor RO Setting limiter low to Setting limiter high
Varies with the setting of the Decimal point
position selection.
⎯
32 Error code RO
Bit data
Bit 0: Adjustment data error
Bit 1: Back-up error
Bit 2: A/D conversion error
Bit 3 and Bit 4: Unused
Bit 5: Custom data error
Bit 6: Unused
Bit 7: Watchdog timer error
Bit 8: Stack overflow
Bit 9 and Bit 10: Unused
Bit 11: Program error (Busy)
Bit 12 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 2471]
⎯
33 Memory area transfer R/W 1 to 8 * 1
34
Control response parameter
R/W
0: Slow
1: Medium
2: Fast
When the P or PD action is selected, this
setting becomes invalid.
PID control,
Position
p
roportioning
PID control: 0
Heat/Cool
PID control: 2
35 Unused
⎯
⎯
⎯
36 Input type R/W
0: TC input K 6: TC input N
1: TC input J 7: TC input T
2: TC input R 8: TC input W5Re/W26Re
3: TC input S 9: TC input PLII
4: TC input B 10: TC input U
5: TC input E 11: TC input L
12: RTD input Pt100 13: RTD input JPt100
14: Current input 0 to 20 mA DC
15: Current input 4 to 20 mA DC
16: Voltage (high) input 0 to 10 V DC
17: Voltage (high) input 0 to 5 V DC
18: Voltage (high) input 1 to 5 V DC
19: Voltage (low) input 0 to 1 V DC
20: Voltage (low) input 0 to 100 mV DC
21: Voltage (low) input 0 to 10 mV DC
24: Voltage (high) input ±1 V DC
25: Voltage (low) input ±100 mV DC
26: Voltage (low) input ±10 mV DC
If changed to Voltage (high) inputs from
TC/RTD/Current/Voltage (low) inputs, select
the hardware by the input selector switch (for
measurement input) at the side of the instrument.
For the selecting procedure, refer to FB100
Instruction Manual (IMR01W16-E) or
FB400/FB900 Instruction Manual
(IMR01W03-E).
Based on
model code.
When not
specifying:
0
* FB100: When the Digital input (DI) assignment (Extension No. 170) value is 6 to 12 and Control area
Local/External transfer
1
is External mode, this data becomes RO (Read only data).
1
Operation of Control area Local/External transfer is only available for FB100.
Continued on the next page.