7. COMMUNICATION DATA LIST
IMR01Y06-E6
59
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
31 Set value (SV) monitor RO Setting limiter low to Setting limiter high
Varies with the setting of the Decimal point
position selection.
32 Error code RO
Bit data
Bit 0: Adjustment data error
Bit 1: Back-up error
Bit 2: A/D conversion error
Bit 3 and Bit 4: Unused
Bit 5: Custom data error
Bit 6: Unused
Bit 7: Watchdog timer error
Bit 8: Stack overflow
Bit 9 and Bit 10: Unused
Bit 11: Program error (Busy)
Bit 12 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 2471]
33 Memory area transfer R/W 1 to 8 * 1
34
Control response parameter
R/W
0: Slow
1: Medium
2: Fast
When the P or PD action is selected, this
setting becomes invalid.
PID control,
Position
p
roportioning
PID control: 0
Heat/Cool
PID control: 2
35 Unused
36 Input type R/W
0: TC input K 6: TC input N
1: TC input J 7: TC input T
2: TC input R 8: TC input W5Re/W26Re
3: TC input S 9: TC input PLII
4: TC input B 10: TC input U
5: TC input E 11: TC input L
12: RTD input Pt100 13: RTD input JPt100
14: Current input 0 to 20 mA DC
15: Current input 4 to 20 mA DC
16: Voltage (high) input 0 to 10 V DC
17: Voltage (high) input 0 to 5 V DC
18: Voltage (high) input 1 to 5 V DC
19: Voltage (low) input 0 to 1 V DC
20: Voltage (low) input 0 to 100 mV DC
21: Voltage (low) input 0 to 10 mV DC
24: Voltage (high) input ±1 V DC
25: Voltage (low) input ±100 mV DC
26: Voltage (low) input ±10 mV DC
If changed to Voltage (high) inputs from
TC/RTD/Current/Voltage (low) inputs, select
the hardware by the input selector switch (for
measurement input) at the side of the instrument.
For the selecting procedure, refer to FB100
Instruction Manual (IMR01W16-E) or
FB400/FB900 Instruction Manual
(IMR01W03-E).
Based on
model code.
When not
specifying:
0
* FB100: When the Digital input (DI) assignment (Extension No. 170) value is 6 to 12 and Control area
Local/External transfer
1
is External mode, this data becomes RO (Read only data).
1
Operation of Control area Local/External transfer is only available for FB100.
Continued on the next page.