Instruction manual

7. COMMUNICATION DATA LIST
IMR01Y06-E6
60
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
37
Setting change rate limiter
(up)
R/W
0 to Input span/unit time * (0: Unused)
Varies with the setting of the Decimal point
position selection.
* Unit time: 60 seconds (Factory set value)
0
38 Control action R/W
0: Brilliant II PID control (Direct action)
1: Brilliant II PID control (Reverse action)
2: Brilliant II Heat/Cool PID control
[water cooling]
3: Brilliant II Heat/Cool PID control
[air cooling]
4: Brilliant II Heat/Cool PID control
[cooling gain linear type]
5: Brilliant II Position proportioning PID
control (Reverse sction)
6: Brilliant II Position proportioning PID
control (Direct sction)
Based on
model code.
When not
specifying: 1
39 Event 1 type R/W
0: None 5: Process high
1
1: Deviation high
1
6: Process low
1
2: Deviation low
1
7: SV high
3: Deviation high/low
1
8: SV low
4: Band
1
9: Unused
10: MV1 high [heat-side]
1,
2
11: MV1 low [heat-side]
1,
2
12: MV2 high [cool-side]
1
13: MV2 low [cool-side]
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in
Position proportioning PID control, set to
the Feedback resistance (FBR) input value.
Based on
model code.
When not
specifying: 0
40 Event 2 type R/W
Based on
model code.
When not
specifying: 0
41 Event 1 differential gap R/W
c Deviation, process or set value:
0 (0.0, 0.00) to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
d MV: 0.0 to 110.0 %
c: TC/RTD:
2, 2.0, or
2.00
V/I: 0.2
d: 0.2
42 Event 2 differential gap R/W
c: TC/RTD:
2, 2.0, or
2.00
V/I: 0.2
d: 0.2
43 Event 1 hold action R/W
0: OFF
1: Hold action ON
(when power turned on;
when transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on;
when transferred from STOP to RUN;
SV changed)
Based on
model code.
When not
specifying: 0
44 Event 2 hold action R/W
Based on
model code.
When not
specifying: 0
45 Unused
46 Output limiter high [MV1] R/W
Output limiter low [MV1] to
+
105.0 %
Position proportioning PID control:
Becomes valid only when there is Feedback
resistance (FBR) input and it does not break.
105.0
Continued on the next page.