7. COMMUNICATION DATA LIST
IMR01Y06-E6
61
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
47 Output limiter low [MV1] R/W
5.0 % to Output limiter high [MV1]
Position proportioning PID control:
Becomes valid only when there is Feedback
resistance (FBR) input and it does not break.
5.0
48 Unused
49 Unused
50
Control loop break alarm
(LBA) time
R/W
0 to 7200 seconds
(0: Unused)
If Event 4 is other than “9: Control loop break
alarm (LBA),” set to RO (Read only data).
480
51
LBA deadband R/W
0 (0.0, 0.00) to Input span
Varies with the setting of the Decimal point
position selection.
If Event 4 is other than “9: Control loop break
alarm (LBA),” set to RO (Read only data).
0, 0.0 or 0.00
52 Unused
53 Unused
54 Event 3 set value (EV3)
R/W
Deviation:
Input span to +Input span
Varies with the setting of the Decimal
point position selection.
Process and set value:
Input scale low to Input scale high
Varies with the setting of the Decimal
point position selection.
Manipulated output value (MV1 or MV2):
5.0 to +105.0 %
If the Event type corresponds to “0: None,”
set to RO (Read only data).
If Event 4 corresponds to “9: Control loop
break alarm (LBA),” the Event 4 set value
becomes RO (Read only data).
50, 50.0 or
50.00
55 Event 4 set value (EV4)
R/W
50, 50.0 or
50.00
56 Event 3 type R/W
0: None
1: Deviation high
1
2: Deviation low
1
3: Deviation high/low
1
4: Band
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Event 3: Unused
Event 4: Control loop break alarm (LBA)
10: MV1 high [heat-side]
1,
2
11: MV1 low [heat-side]
1,
2
12: MV2 high [cool-side]
1
13: MV2 low [cool-side]
1
1
Event hold action is available.
2
If there is Feedback resistance (FBR) input in
Position proportioning PID control, set to
the Feedback resistance (FBR) input value.
Based on
model code.
When not
specifying: 0
57 Event 4 type R/W
Based on
model code.
When not
specifying: 0
Continued on the next page.