Instruction manual
7. COMMUNICATION DATA LIST
IMR01Y06-E6
62
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
58 Event 3 differential gap R/W
c Deviation, process or set value:
0 (0.0, 0.00) to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
d MV: 0.0 to 110.0 %
c: TC/RTD:
2, 2.0, or
2.00
V/I: 0.2
d: 0.2
59 Event 4 differential gap R/W
c: TC/RTD:
2, 2.0, or
2.00
V/I: 0.2
d: 0.2
60 Event 3 hold action R/W
0: OFF
1: Hold action ON
(when power turned on;
when transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on;
when transferred from STOP to RUN;
SV changed)
Based on
model code.
When not
specifying: 0
61 Event 4 hold action R/W
Based on
model code.
When not
specifying: 0
62
Setting change rate limiter
(down)
R/W
0 to Input span/unit time *
(0: Unused)
Varies with the setting of the Decimal
point position selection.
* Unit time: 60 seconds (Factory set value)
0
63 Comprehensive event state RO
Bit data
Bit 0: Burnout Bit 5: Event 3
Bit 1: Event 1 Bit 6: Event 4
Bit 2: Event 2 Bit 7: HBA 2
Bit 3: HBA 1 Bit 8: FBR burnout
Bit 4: LBA Bit 9 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
⎯
64
Remote setting (RS) input
value monitor
RO Setting limiter low to Setting limiter high
Varies with the setting of the Decimal point
position selection.
⎯
65
Unused
⎯ ⎯ ⎯
66
Uuused
⎯ ⎯ ⎯
67
Burnout state monitor of
feedback resistance (FBR)
input
RO 0: OFF
1: ON
⎯
68
Memory area soak time
monitor
RO
0 to 11999 seconds or 0 to 5999 minutes
Data range of Area soak time can be selected
on the Soak time unit.
⎯
69
Digital input (DI) state
monitor
RO
Bit data
Bit 0: DI1 Bit 4: DI5
Bit 1: DI2 Bit 5: DI6 *
Bit 2: DI3 Bit 6: DI7 *
Bit 3: DI4 Bit 7 to Bit 15: Unused
Data 0: Contact open
1: Contact closed
[Decimal number: 0 to 127]
* Unused on the FB100.
⎯
Continued on the next page.