Instruction manual

7. COMMUNICATION DATA LIST
IMR01Y06-E6
62
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
58 Event 3 differential gap R/W
c Deviation, process or set value:
0 (0.0, 0.00) to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
d MV: 0.0 to 110.0 %
c: TC/RTD:
2, 2.0, or
2.00
V/I: 0.2
d: 0.2
59 Event 4 differential gap R/W
c: TC/RTD:
2, 2.0, or
2.00
V/I: 0.2
d: 0.2
60 Event 3 hold action R/W
0: OFF
1: Hold action ON
(when power turned on;
when transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on;
when transferred from STOP to RUN;
SV changed)
Based on
model code.
When not
specifying: 0
61 Event 4 hold action R/W
Based on
model code.
When not
specifying: 0
62
Setting change rate limiter
(down)
R/W
0 to Input span/unit time *
(0: Unused)
Varies with the setting of the Decimal
point position selection.
* Unit time: 60 seconds (Factory set value)
0
63 Comprehensive event state RO
Bit data
Bit 0: Burnout Bit 5: Event 3
Bit 1: Event 1 Bit 6: Event 4
Bit 2: Event 2 Bit 7: HBA 2
Bit 3: HBA 1 Bit 8: FBR burnout
Bit 4: LBA Bit 9 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
64
Remote setting (RS) input
value monitor
RO Setting limiter low to Setting limiter high
Varies with the setting of the Decimal point
position selection.
65
Unused
66
Uuused
67
Burnout state monitor of
feedback resistance (FBR)
input
RO 0: OFF
1: ON
68
Memory area soak time
monitor
RO
0 to 11999 seconds or 0 to 5999 minutes
Data range of Area soak time can be selected
on the Soak time unit.
69
Digital input (DI) state
monitor
RO
Bit data
Bit 0: DI1 Bit 4: DI5
Bit 1: DI2 Bit 5: DI6 *
Bit 2: DI3 Bit 6: DI7 *
Bit 3: DI4 Bit 7 to Bit 15: Unused
Data 0: Contact open
1: Contact closed
[Decimal number: 0 to 127]
* Unused on the FB100.
Continued on the next page.