7. COMMUNICATION DATA LIST
IMR01Y06-E6
63
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
70
Operation mode state
monitor
RO
Bit data
Bit 0: Control STOP
Bit 1: Control RUN
Bit 2: Manual mode *
Bit 3: Remote mode *
Bit 4 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
* During operation in Manual mode, the
Manual mode of the Operation mode state
monitor is set to the “1: ON” state and the
Remote mode of the same monitor is set to
the “0: OFF” state even if the parameter,
Remote/Local transfer is set to “1: Remote
mode.”
71 Unused
72 Unused
73 Unused
74
Output state monitor
RO
Bit data
Bit 0: OUT1 Bit 4: DO3 *
Bit 1: OUT2 Bit 5: DO4 *
Bit 2: DO1 Bit 6 to Bit 15: Unused
Bit 3: DO2
Data 0: OFF 1: ON
[Decimal number: 0 to 63]
* Unused on the FB100.
75
Current transformer 2 (CT2)
input value monitor
RO 0.0 to 30.0 A (CTL-6-P-N)
0.0 to 100.0 A (CTL-12-S56-10L-N)
76 Unused
y
y
y
89
90
Remote/Local transfer
R/W
0: Local mode
1: Remote mode
When performing remote control by remote
setting input and also performing Cascade
control and Ratio setting via intercontroller
communication, transfer to the Remote mode.
[FB100]
When the Remote setting (RS) input is not
provided, this data becomes RO (Read only
data).
0
91 Unused
y
y
y
109
110 Link area number R/W 0 to 8 (0: No link)
[FB100]
When the Digital input (DI) assignment
(Extension No. 170) value is 6 to 12, this
data becomes RO (Read only data).
0
Continued on the next page.