Instruction manual

7. COMMUNICATION DATA LIST
IMR01Y06-E6
64
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
111 Area soak time R/W
0 to 11999 seconds or
0 to 5999 minutes
Data range of Area soak time can be selected
on the Soak time unit.
[FB100]
When the Digital input (DI) assignment
(Extension No. 170) value is 6 to 12, this data
becomes RO (Read only data).
0
112
Integral time
[cool-side]
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action)
[both heat-side and cool-side]
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID control,
set to RO (Read only data).
240
113
Derivative time
[cool-side]
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID control,
set to RO (Read only data).
60
114 Unused
y
y
y
127
128
Manual reset
R/W
100.0 to +100.0 %
The offset can be manually eliminated.
If the Integral function is valid, set to RO
(Read only data).
0.0
129 Unused
y
y
y
139
140
Heater break determination
point 1
R/W
0.0 to 100.0 % of HBA1 set value
(0.0: Heater break determination is invalid)
If there is no Current transformer 1 (CT1) or
CT1 is assigned to “0: None,” set to RO (Read
only data).
If Heater break alarm 1 (HBA1) corresponds
to “0: Type A,” set to RO (Read only data).
30.0
141
Heater melting
determination point 1
R/W
0.0 to 100.0 % of HBA1 set value
(0.0: Heater melting determination is invalid)
If there is no Current transformer 1 (CT1) or
CT1 is assigned to “0: None,” set to RO (Read
only data).
If Heater break alarm 1 (HBA1) corresponds
to “0: Type A,” set to RO (Read only data).
30.0
142 PV ratio R/W 0.500 to 1.500 1.000