7. COMMUNICATION DATA LIST
IMR01Y06-E6
75
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
279
Integral time adjusting
factor [cool-side]
R/W
0.01 to 10.00 times
1.00
280
Derivative time adjusting
factor [cool-side]
R/W 1.00
281
Proportional band limiter
high [heat-side]
R/W
TC/RTD inputs:
0 to Input span, 0.0 to Input span or
0.00 to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span
TC/RTD:
Input span
V/I: 1000.0
282
Proportional band limiter
low [heat-side]
R/W
TC/RTD:
0, 0.0 or 0.00
V/I: 0.0
283
Integral time limiter high
[heat-side]
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
3600
284
Integral time limiter low
[heat-side]
R/W 0
285
Derivative time limiter high
[heat-side]
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
3600
286
Derivative time limiter low
[heat-side]
R/W 0
287
Proportional band limiter
high [cool-side]
R/W
TC/RTD inputs:
1 to Input span, 0.1 to Input span or
0.01 to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of input span
TC/RTD:
Input span
V/I: 1000.0
288
Proportional band limiter
low [cool-side]
R/W
TC/RTD:
1, 0.1 or 0.01
V/I: 0.1
289
Integral time limiter high
[cool-side]
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
3600
290
Integral time limiter low
[cool-side]
R/W 0
291
Derivative time limiter high
[cool-side]
R/W
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
3600
292
Derivative time limiter low
[cool-side]
R/W 0
293 Unused
y
y
y
299
300
Setting change rate limiter
unit time
R/W
1 to 3600 seconds
60
301
Soak time unit
R/W
0: 0 to 5999 minutes
1: 0 to 11999 seconds
Set the data range of Memory area soak time
monitor and Area soak time.
1
302 Unused
y
y
y
319
320
STOP display
R/W
0:
STO
P
is displayed on the PV display.
1:
STOP is displayed on the SV display.
1
Continued on the next page.