7. COMMUNICATION DATA LIST
IMR01Y06-E6
77
Continued from the previous page.
Extension
number
Communication item
Attri-
bute
Data range
Factory
set value
343
Power feed forward input
value monitor
[Unused on the FB100]
RO
0.0 to 160.0 %
Display in the percentage of the load voltage
(Rated value).
344 Unused
y
y
y
349
350
Startup tuning (ST)
R/W
0: ST unused
1: Execute once *
2: Execute always
* When the Startup tuning (ST) is finished,
the setting will automatically returns to
“0: ST unused.”
The Startup tuning (ST) function is activated
according to the ST start condition selected.
If control is other than Position proportioning
PID control, set to RO (Read only data).
0
351
ST proportional band
adjusting factor
R/W
0.01 to 10.00 times
1.00
352
ST integral time adjusting
factor
R/W 1.00
353
ST derivative time adjusting
factor
R/W 1.00
354
ST start condition
R/W
0: Activate the Startup tuning (ST) function
when the power is turned on; when
transferred from STOP to RUN; or when
the Set value (SV) is changed.
1: Activate the Startup tuning (ST) function
when the power is turned on; or when
transferred from STOP to RUN.
2: Activate the Startup tuning (ST) function
when the Set value (SV) is changed.
0
355
Automatic temperature rise
group
R/W
0 to 16
(0: Automatic temperature rise function OFF)
0
356
Automatic temperature rise
learning
R/W
0: Unused
1: Learning *
* When the Automatic temperature rise
learning is finished, the setting will
automatically returns to “0: Unused.”
If the Automatic temperature rise group
corresponds to “0: Automatic temperature rise
function OFF,” set to RO (Read only data).
1
357
Automatic temperature rise
dead time
R/W
0.1 to 1999.9 seconds
10.0
358
Automatic temperature rise
gradient data
R/W
1 (0.1, 0.01) to Input span/minutes
Varies with the setting of the Decimal point
position selection.
1, 1.0 or 1.00
359
RUN/STOP group
R/W
0 to 16
(0: Group RUN/STOP function OFF)
0
Continued on the next page.