Instruction manual

8. USAGE EXAMPLE
IMR01Y06-E6
83
8.3 Use Instruments Setting
Set the PLC, COM-JC and controller as the following.
PLC setting
For operating of CC-Link system master local unit QJ61BT11N and MELSEC sequencer
programming software GX Developer, refer to PLC Instruction Manual.
[CC-Link system master local unit QJ61BT11N setting]
Setting item Content
Station number 0
CC-Link communication speed 156 kbps
[Master station network parameter setting by GX Developer]
Setting item Content
Number of boards in module 1
Start I/O number 0000
Operational settings
Parameter name: None
Data link disorder station setting: Clear
Case of CPU STOP setting: Refresh
Type Master station
CC-Link mode setting Remote net (Ver. 1 mode)
Total number of connected
modules
1
Number of retries 5
Number of automatic return
modules
1
Standby master station number Blank
Operation specification when
CPU is down
Stop
Scan mode specification Asynchronous
Delay time setting
10 (500 μs)
Station information
[Number of COM-JC connection:
1 (Station number: 1)]
Station type: Remote device station
Expanded cyclic setting: Single
Number of occupied station: Occupies 1 station
Remote station points: 32 points
Reserved/Invalid station select: No setting
Intelligent buffer select (word): No setting
CC-Link version varies according to the specification of Occupied station/Extended cyclic of
the COM-JC. Select CC-Link version of PLC by setting the following CC-Link specifications:
1 station occupied 1 time/4 stations occupied 1 time: CC-Link Ver. 1.10
4 stations occupied 2 times: CC-Link Ver. 2.00