Instruction manual

8. USAGE EXAMPLE
IMR01Y06-E6
84
[Automatic refresh parameter setting by GX Developer]
Setting item Content
Remote input (RX) refresh device X1000
Remote output (RY) refresh device Y1000
Remote register (RWr) refresh device W0
Remote register (RWw) refresh device W100
Special relay (SB) refresh device SB0
Special register (SW) refresh device SW0
COM-JC setting
[CC-Link communication conditions]
Number of occupied station/extended cyclic:
1 station occupied 1 time (2 controllers assignment)
Station number: 1
CC-Link communication speed: 156 kbps
[Controller communication condition]
Controller communication speed: 19200 bps (Factory set value)
For setting procedure, refer to 5. SETTING (P. 16).
Controller setting
[Controller communication conditions: Use communication 1 side]
Device address: 1 (Controller 1) and 2 (Controller 2)
Communication protocol: Modbus-RTU
Communication speed: 19200 bps (Factory set value)
Data bit configuration: Data 8-bit, Without parity bit, Stop 1-bit
For setting procedure, refer to FB400/FB900 Communication Quick Manual
(IMR01W07-E).