Instruction manual

8. USAGE EXAMPLE
IMR01Y06-E6
90
Continued from the previous page.
Continued on the next page.
Set the extension number for display.
Extension number 0: Turn off the
extension number setting Bit 0
(Y1000: RY00) for Measured value
(PV) display.
RST Y1000
X101B M0 M1
When the COM-JC is in the remote ready state and no display extension
number setting is processed yet.
Remote ready (X101B: RX1B) ON
Extension number setting flag for display (M0) OFF
SET Y1000
M1
When Measured value (PV)/Manipulated output
value (M1) is transferred to Manipulated out
p
ut
value (M1).
RST Y100C
SET Y100C
X100C
The Extension display completion flag (X100C: RX0C) is
turned OFF.
Set the extension number for display.
Extension number 1: Turn on the
extension number setting Bit 0 (Y1000:
RY00) for Manipulated output value
(MV1) display.
Turn off the Extension display flag
(Y100C: RY0C).
Turn on the Extension display flag
(Y100C: RY0C).
When Measured value (PV)/Manipulated output
value (M1) is transferred to Measured value (PV).
SET M0
Extension number setting end for
display.
Turn on the Extension number setting
flag for display (M0).
Store the Measured value (PV) of
controller 1 into the data register D0.
Store the Extension area for display
(W002: RWr2) of controller 1 into the
data register D0.
X100C M0 M1
When the extension display is finished and the display extension
number has been set.
Extended display completion flag (X100C: RX0C) ON
Extension number setting flag for display (M0) ON
When Measured value (PV)/Manipulated
output value (M1) is transferred to Measured
value (PV).
MOV W2 D0
MOV W3 D1
Store the Measured value (PV) of
controller 2 into the data register D1.
Store the Extension area for display
(W003: RWr3) of controller 1 into the
data register D1.
Only the bit (Bit 0) necessary for
setting display extension number
0 or 1 is specified. Any
unspecified bit is assumed to be
the register initial value, 0.