Specifications

Temperature Controller Driver
GP-Pro EX Device/PLC Connection Manual
183
6.3 HA Series
This address can be specified as system data area.
<Communication identifier list>
Device Bit Address Word Address
32
bits
Notes
Communication identifier 0000.00-00E6.1F 0000-00E6
*1
*2
*3
*1 There are cases for which writing is not available depending on the device address. Check the
identifying attributes of the external device’s manual before use.
*2 When bit is written, the indicator reads the corresponding word address of external device, assign
a bit to the read word address, and return to the external device. There are cases when correct data
cannot be written if the word address is written using a ladder program, while the indicator reads
data of the external device and sends it back.
*3 32-bit device
Address Identifier Description
00 M1 Input 1 measured value (PV1)
01 M0 Input 2 measured value (PV2)
02 M2 Feedback resistance input monitor
03 M3 Current transformer 1 (CT1) input value monitor
04 M4 Current transformer 2 (CT2) input value monitor
05 MS Input 1 setting-value(SV1) monitor
06 MT Input 2 setting-value(SV1) monitor
07 S2 Remote setting (RS) input value monitor
08 KH Cascade monitor
09 B1 Burnout state monitor of input 1
0A B0 Burnout state monitor of input 2
0B B2 Burnout state monitor of feedback resistance input
0C AA Event 1 state monitor
0D AB Event 2 state monitor
0E AC Event 3 state monitor
0F AD Event 4 state monitor
10 AE Heater break alarm 1 (HBA1) state
11 AF Heater break alarm 2 (HBA1) state
12 O1 Manipulated output value (MV1) of input 1
13 O0 Manipulated output value (MV2) of input 2
14 ER Error code
15 L1 Event input(DI) state
16 L0 Operation mode state
17 TR Memory area soak time monitor
18 G1 PID/AT transfer of input 1
19 G0 PID/AT transfer of input 2
1A J1 Auto/Manual transfer of input 1
1B J0 Auto/Manual transfer of input 2
1C C1 Remote/Local transfer
1D SR RUN/STOP transfer
1E ZA Memory area transfer
1F A1 Event 1 set value
20 A2 Event 2 set value
21 A3 Event 3 set value
22 A5 Control loop break alarm 1 (LBA1) time