Specifications

Temperature Controller Driver
GP-Pro EX Device/PLC Connection Manual
230
<Communication identifier list>
continued to next page
Address Identifier
Description
Address Identifier
Description
00 VR ROM version 32 A7 Heater break alarm (HBA) set value
01 VR ROM version 33 NE Heater break determination point
02 M1 Measured value (PV) 34 NF Heater melting determination point
03 AJ Comprehensive event state 35 PB PV bias
04 L0 Operation mode state monitor 36 F1 PV digital filter
05 ER Error code 37 PR PV ratio
06 O1
Manipulated output value (MV) monitor [heat-side]
38 DP PV low input cut-off
07 O2
Manipulated output value (MV) monitor [cool-side]
39 RB RS bias
08 M3
Current transformer (CT) input value monitor
3A F2 RS digital filter
09 MS Set value (SV) monitor 3B RR RS ratio
0A S2
Remote setting (RS) input value monitor
3C DV Output distribution selection
0B B1 Burnout state monitor 3D DW Output distribution bias
0C AA Event 1 state monitor 3E DQ Output distribution ratio
0D AB Event 2 state monitor 3F T0 Proportional cycle time
0E AC Event 3 state monitor 40 VI
Minimum ON/OFF time of proportioning cycle
0F AD Event 4 state monitor 41 ON Manual manipulated output value
10 AE
Heater break alarm (HBA) state monitor
42 RV Area soak time stop function
11 Q1 Output state monitor 43 NG EDS mode (for disturbance 1)
12 TR
Memory area soak time monitor
44 NX EDS mode 2 (for disturbance 2)
13 UT Integrated operating time monitor 45 NI EDS value 1 (for disturbance 1)
14 Hp
Holding peak value ambient temperature monitor
46 NJ EDS value 1 (for disturbance 2)
15 EM Backup memory state monitor 47 NK EDS value 2 (for disturbance 1)
16 ED Logic output monitor 1 48 NM EDS value 2 (for disturbance 2)
17 EE Logic output monitor 2 49 NN EDS transfer time (for disturbance 1)
18 G1 PID/AT transfer 4A NO EDS transfer time (for disturbance 2)
19 J1 Auto/Manual transfer 4B NQ EDS action time (for disturbance 1)
1A C1 Remote/Local transfer 4C NL EDS action time (for disturbance 2)
1B SR RUN/STOP transfer 4D NR
EDS action wait time (for disturbance 1)
1C ZA Memory area transfer 4E NY
EDS action wait time (for disturbance 2)
1D AR Interlock release 4F NT EDS value learning times
1E A1 Event 1 set value (EV1) 50 NU EDS start signal
1F A2 Event 2 set value (EV2) 51 EI Operation mode
20 A3 Event 3 set value (EV3) 52 ST
Startup tuning (ST)
21 A4 Event 4 set value (EV4) 53 Y8 Automatic temperature rise learning
22 A5
Control loop break alarm (LBA) time
54 EF Communication switch for logic
23 N1 LBA deadband 55 XI Input type
24 S1 Set value (SV) 56 PU Display unit
25 P1 Proportional band [heat-side] 57 XU Decimal point position
26 I1 Integral time [heat-side] 58 XV Input scale high
27 D1 Derivative time [heat-side] 59 XW Input scale low
28 CA Control response parameter 5A AV Input error determination point (high)
29 P2 Proportional band [cool-side] 5B AW Input error determination point (low)
2A I2 Integral time [cool-side] 5C BS Burnout direction
2B D2 Derivative time [cool-side] 5D XH Square root extraction
2C V1 Overlap/Deadband 5E E0
Output assignment (Logic output selection function)
2D MR Manual reset 5F NA
Energized/De-energized (Logic output selec-
tion function)
2E HH Setting change rate limiter (up) 60 XA Event 1 type
2F HL Setting change rate limiter (down) 61 FA Event 1 channel setting
30 TM Area soak time 62 WA Event 1 hold action
31 LP Link area number 63 LF Event 1 interlock