Specifications

Temperature Controller Driver
GP-Pro EX Device/PLC Connection Manual
71
Settings of External Device
Communication setting of the external device is set with the SET, MODE, UP and Down keys located on the front
face of the temperature controller.
Please refer to the temperature controller manual for details.
Procedure
1. Press the SET key for 2 seconds to change from PV display mode to engineer setting mode.
Parameter group is displayed.
2. Press the Up/Down keys to display the parameter group, "PG60."
3. Press the SET Key to display setting item. Every time the SET Key is depressed, item to be set switches.
4. Press the Up/Down keys to select set value, and press the SET Key.
5. Press the Reset key to reset the external device.
6. Press the Monitor/Mode key and the SET key at the same time to move to SETUP setting mode.
7. Press the SET key several times to display Add.
8. Press the Up/Down keys to select set value, and press the SET key.
9. Press the RUN/HOLD key to move to operation monitor mode.
Setting value
Engineer setting mode
SETUP setting mode
bPS 2
bIT 0
Add 0
Parameters to be set differ per temperature controller. Please refer to the temperature controller
manual for details.