Ba ery Type Selection
AGM/GEL : Sealed type (VRLA) , AGM-GEL , Maintenance Free , Automotive or Deep Cycle lead acid
ba eries
WET : Flooded Type lead acid ba eries (to which water can be added) Automotive or Deep Cycle
Calcium-Calcium : Sealed type (VRLA) Lead Acid ba eries with Calcium content Automotive or Deep Cycle
B1. FLOAT VOLTAGE SELECTION
These fi ne tuned selections of fl oat voltages enable the best voltage level for maximum ba ery life. Choose 13.8V when in doubt
or in Power Supply Mode.
Follow the markings on Deep Cycle ba eries of the Standby fl oat voltage.
B2. Recommended Ba ery Capacity
The following minimum AH capacities are a generalized suggestion, some ba eries can take higher charge current, check with
ba ery manufacturers for charging ba eries with smaller capacity.
C. Ba ery Charger Installation and Connection
Observe the warnings & safety precautions before rushing to install and operate the charger.
Check ba ery condition, fi ll up cells for wet ba ery, clean ba ery poles.
Secure the ba ery charger in a well ventilated place, make sure the mounting surface is fl at and without so covering material or
loose paper sheet. The air intake is at the bo om and air outlet at the back. Make sure both intake and outlet are not blocked.
Never place charger on top of ba ery.
Plug in the AC mains and turn on Power Switch , the Charger On LED and the Float LED should be on green indicating Charger is in
good order for charging lead acid ba ery.
Before connecting or disconnecting the charging cable, turn off the Power Switch and unplug AC cord from the mains.
First connect the Red cable to Positive + terminal of charger and the ba ery Positive + Pole. Then connect the Black cable to the
Negative – terminal and the Negative – Pole of the ba ery.
Make sure all the connections are secured and well tighten up, double check on the correct polarity.
Double check again for correct selection of Slide Switch 1 at Charger Mode, Switch 2 for Ba ery type and Switch 3 for Float Voltage
se ing value.
D. Normal 3 Stage (IUoU) Charging Operation
The 3 stage IU0U charge algorithm ensures fast , complete and at the same time gentle charging of the lead acid ba ery.
Charger Model
Ba ery Capacity
RND 305-00017 RND 305-00016
40 Ah - 100 Ah
80 Ah - 200 Ah