SECTION 5: HEATER INSTALLATION
7
SECTION 5: HEATER INSTALLATION
5.1 General
Heaters are designed for installation above 1.8 m.
These heaters must be installed within the heated
space. Duct delivery systems are not permitted with
axial fans. When handling or supporting the heater
from below, ensure that the weight is taken at the
support points.
5.2 Shelf Mounting and Suspension
For typical suspension, See Page 7, Figure 2.
5.3 Wall Mounting
For typical suspension, See Page 8, Figure 3.
Heaters blowing parallel to the wall can only be
installed with the service door away from the wall.
The wall mounting brackets must be attached to a
suitable wall through all mounting holes. Screw
sizes less than M10 may not be used. In order for
the wall mounting brackets to adequately carry the
weight of the heater, it must be installed with best
building practice.
Figure 2: Suspension Methods
Existing cabinet screws must be re-used.
WARNING
Crush Hazard
Use 10 mm steel drop rod
minimum.
Failure of the supports can
result in death, injury
or property damage.
Cone Point
Set Pin
Window
Clamp
Unistrut
10 mm
Steel
Drop Rod
Nut
Washer
Riv
Nut
Support Points
Ensure all suspension hardware
is torqued to a minimum
of 27 Nm (20 ft lbs).
NOTE: For vertical installations, use the mounting points on the rear of the unit.
10 mm
Steel
Drop Rod
Washer
Nut
Unistrut
Channel Nut
Shelf Mounting
Brackets
Description Part Number Qty.
Shelf Mounting Bracket
Kit
111115 10K
Sh e lf M ou n t in g B r acke t ( 2) 1111115 10 2
Screw #10 x 1/2"
Type AB Phil HWH Z (2)
94311008 2