Quick Start Guide Owner's manual

PE PE
R
(L1)
TE
S
(L2)
T
(L3)
U
(T1)
V
(T2)
W
(T3)
DC
+
DC
Dynamic Brake
Required
Input Fusing
Required Branch
Circuit Disconnect
Shield
Common Mode Core*
Diagram shows connections that are common for all drives.
Refer to User Manual for Detailed Information.
Ground per
Local Codes
Motor Frame
Motor
Terminator*
PE
* Optional
Nearest
Building Structure Steel
AC Input
to Drive
PE
Ground
TE
Ground
Drive Output
to Motor
(Not on all drives) (Not on all drives)
Conduit/4-Wire Cable
BRK
Important: Verify motor insulation system peak voltage
rating. For cable lengths greater than 6.1
meters (20 feet), consult the User Manual.
Power Wiring – TB1
Digital Outputs – TB2
Only Present
on B Frame
& Up Drives
Reserved for
Future Use
CR2
CR1 CR3CR3 CR4CR4
10
11 12 13 14 15 16 17 18 A1 A2
Terminal
TE
10, 11
11, 12
13, 14
14, 15
16, 17
17, 18
A1, A2
Signal
True Earth - Shield Termination
CR1 Programmable Contact
CR2 Programmable Contact
CR3 Programmable Contact
CR4 Programmable Contact
Reserved for Future Use
Resistive Rating = 115V AC/30V DC, 5.0A
Inductive Rating = 115V AC/30V DC, 2.0A
Contacts Shown in Unpowered State
(or Powered State with Fault/Alarm Present)
Important: On A Frame Drives, the power supply used for relay contact outputs requires a field installation of
transient voltage surge suppression with maximum clamping voltage of 2.5 kV on all control boards.
1336 PLUS II Quick Start Guide
This Quick Start Guide summarizes the basic steps needed to install, start-up and program the 1336 PLUS II Adjustable
Frequency AC Drive. The information provided Does Not replace the User Manual and is intended for qualif
ied drive service
personnel
only. Refer to the 1336
PLUS II User Manual (publication 1336 PLUS-5.3) for details on other application
considerations and related precautions.
Publication 1336 PLUS-5.9ML – June, 2003 P/N 188747 (06)
Supersedes January, 2002 Copyright © 2003 Rockwell Automation, Inc. All rights reserved. Printed in USA.