Installation Instructions IN Allen-Bradley 1397 Enhanced Field Supply Card Cat. Nos. 1397-FS1010 1397-FS1020 What This Option Provides When installed, the Enhanced Field Supply Card provides greater control over the field output for 230V Drives, allowing the user to directly match the rated DC motor field voltage. Where This Option Is Used This option may be used with all 230V 1397 Drives.
1397 Enhanced Field Supply Card Installation ! ! ATTENTION: This board contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control precautions are not followed. If you are not familiar with static control procedures, reference AB publication 8000-4.5.2, “Guarding against Electrostatic Damage” or any other applicable ESD protection handbook.
1397 Enhanced Field Supply Card Installation (continued) 3 ❏ 3 For 1.5-30HP Drives, loosen the captive carrier retaining screw to swing the carrier door open. Captive Carrier Screw 1.5-30HP Drives with Carrier Door Closed ❏ 4a For 40-75HP Drives without an AC line disconnect, loosen the (2) auxiliary panel cover retaining screws. To lift out the auxiliary panel, loosen the screws only enough to allow the panel tabs to slide out.
1397 Enhanced Field Supply Card Installation (continued) ❏ 4b For 40-75HP Drives with an AC line disconnect, both the disconnect switch and disconnect panel must be removed. 45 AC AC Line Disc. Line Disc. Mounting Mounting Screw Screw 81 82 83 A1 A1 GRD P4 P4 P4 S4 S4 S4 ON AC Line Disc. Mounting SET AT "2" Screw OFF AC Line Disc.
1397 Enhanced Field Supply Card Installation 5 ❏ 5 To remove either the Fixed or Regulated Field Supply, remove the (4) retaining screws from the outside right side panel. (continued) Outside Right Side Panel Retaining Screw Retaining Screw Retaining Screw Retaining Screw 1.5-30HP Drives Retaining Screw Retaining Screw Retaining Screw Retaining Screw Retaining Screw Retaining Screw Retaining Screw Retaining Screw 100-150HP Drives 40-75HP Drives 1397–5.
1397 Enhanced Field Supply Card Installation ❏ 6 Unplug the (5) blue fast-on connectors from the Fixed or Regulated Field Supply Card. (continued) • For the Fixed Field Supply, unplug the red P4 connector from the Power Interface Board to free the card. • For the Regulated Field Supply, unplug the Regulated Field Supply cable assembly at Regulator Board Connector J25 to route the cable back through the carrier door.
1397 Enhanced Field Supply Card Installation 7 ❏ 8 For 1.5-30HP Drives, plug the Enhanced Field Supply connector P4 into Power Interface Board connector P4. For 40-150HP Drives, plug the Enhanced Field Supply connector P4 into Power Interface Board connector S4. (continued) 82 83 S4 S4 S4 81 P4 P4 P4 P4 P4 P4 S4 S4 S4 P4 P4 P4 P P 4 P4 4 P4 1.
1397 Enhanced Field Supply Card Installation ❏ 9 Replace fuses 6FU, 7FU & 8FU with the (3) UL Class CC/600V/25A fuses included with the kit. (continued) 810903-2424 DANGER CIRCUIT BREAKER DOES NOT DISCONNECT INCOMING A0 LINE POWER IT ONLY PROVIDES DC FAULT PROTECTION. LE DISCONECTEUR NE COUPTE PAS L'AUTOMENTATION DU SPOTEUR IL NES SERT QUE A ASSURER UNE PROTECTION CONTRE LES DESFAULTS DC. 6FU 7FU 8FU DANGER P/N 33145 ! RISK OF ELECTRICAL SHOCK. DISCONNECT INPUT POWER BEFORE SERVICING EQUIPMENT.
1397 Enhanced Field Supply Card Installation (continued) ❏ 10 If required, reinstall the auxiliary panel cover or AC line disconnect removed in steps 4a & 4b. Torque the (3) bus bar fasteners to the values listed below. Fastener Size 1 ⁄ 4” 3 ⁄ 8” Setup 9 Maximum Torque 7.46 N-m (66 lb.-in.) 26.66 N-m (236 lb.-in.) (3) drive parameters, Jumper 21 on the drive’s Regulator Board, and the Enhanced Field Supply Card’s jumper wire must be set to configure the Enhanced Field Supply Card. P.
1397 Enhanced Field Supply Card Setup P.272 E-Fld Volts Adj (continued) Parameter P.272 [E-Fld Volts Adj] is used to match the drive’s rated field voltage to different DC motor field voltages. A field voltage below the motor’s rated value can operate the motor above rated base speed with reduced torque. A voltage above the motor’s rated base speed however, could also result in armature overvoltage and overheating of the motor’s field windings.
1397 Enhanced Field Supply Card 11 P4 4 P 4 P B-C Jumper Settings 707973-5R X1 X2 H1 H2 Drive Input Volts Enhanced Field Supply Jumper Set to B-C Minimum Output Maximum Output Motor Field Volts Motor Field Volts 230V AC 0.45V DC 0.9V DC LINE 1 2 3 4 5 6 7 8 9 000 0.4502 0.4502 0.4503 0.4505 0.4507 0.4510 0.4514 0.4518 0.4523 0.4529 583 010 0.4536 0.4543 0.4551 0.4559 0.4568 0.4578 0.4589 0.4600 0.4612 0.4624 581 020 0.4637 0.4651 0.4665 0.4681 0.4696 0.
Rockwell Automation helps its customers receive a superior return on their investment by bringing together leading brands in industrial automation, creating a broad spectrum of easy-to-integrate products. These are supported by local technical resources available worldwide, a global network of system solutions providers, and the advanced technology resources of Rockwell. Worldwide representation.