XM-940 Dynamic Measurement Terminal Base Catalog Number 1440-TB-A Installation Instructions FOR XM-120...
XM-940 Dynamic Measurement Terminal Base Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.
XM-940 Dynamic Measurement Terminal Base 3 ATTENTION Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment.
XM-940 Dynamic Measurement Terminal Base ATTENTION Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wrist strap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment.
XM-940 Dynamic Measurement Terminal Base 5 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations. Informations sur l’utilisation de cet équipement en environnements dangereux. Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only.
XM-940 Dynamic Measurement Terminal Base European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the Ex Marking.
XM-940 Dynamic Measurement Terminal Base 7 WARNING • This equipment shall be mounted in an ATEX-certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in IEC 60664-1) when applied in Zone 2 environments. The enclosure must have a tool-removable cover or door.
XM-940 Dynamic Measurement Terminal Base IMPORTANT There are no drawings associated with the XM-124 Standard Dynamic Measurement Module, catalog number 1440-SDM02-01RA. Be sure that the installer follows all applicable local and regional requirements for installation of the product in the planned location and environment. Power Requirements Refer to the XM-124 Standard Dynamic Measurement installation guide, publication 1440-IN001, for specific power consumption and other requirements.
XM-940 Dynamic Measurement Terminal Base 9 Wiring Requirements Use solid or stranded wire. All XM wiring should meet the following specifications: • 0.34…2.1 mm2 (22…14 AWG) copper conductors without pretreatment; 8.4 mm2 (8 AWG) required for grounding the DIN rail for electromagnetic interference (EMI) purposes • Recommended strip length 8 mm (0.31 in.
XM-940 Dynamic Measurement Terminal Base XM System DIN Rail Grounding 1 1440-VST02-01RA DYNAMIC MEASUREMENT 1440-REX00-04RD EXPANSION RELAY 1440-VST02-01RA DYNAMIC MEASUREMENT 1440-REX00-04RD EXPANSION RELAY Power Supply 2 2 1440-RMA00-04RC MASTER RELAY 1440-REX00-04RD EXPANSION RELAY 1440-TSP02-01RB POSITION 1440-REX00-04RD EXPANSION RELAY 2 1 1440-VST02-01RA DYNAMIC MEASUREMENT 1440-REX00-04RD EXPANSION RELAY Power Supply 1 Use 2.1 mm2 (14 AWG) wire. 2 Use 8.4 mm2 (8 AWG) wire.
XM-940 Dynamic Measurement Terminal Base 11 The grounding wire can be connected to the DIN rail by using a DIN Rail Grounding Block (see illustration below). DIN Rail Grounding Block 1 1 Use 8.4 mm2 (8 AWG) wire. 24V Common Grounding 24V to the XM module must be grounded. When two or more power supplies power the XM system, ground the 24V Commons at a single point, such as the ground bus bar.
XM-940 Dynamic Measurement Terminal Base IMPORTANT The 24V Common and Signal Common terminals are internally connected. They are isolated from the Chassis terminals unless they are connected to ground as described in this manual. See Wiring on page 17 for terminal assignments. Transducer Grounding Make certain the transducers are electrically isolated from earth ground. Cable shields must be grounded at one end of the cable, and the other end left floating or not connected.
XM-940 Dynamic Measurement Terminal Base 13 DeviceNet Grounding - XM-124 Module Only The DeviceNet network is fully isolated from the XM-124 power and ground circuits. Therefore, DeviceNet network can be powered from any suitable DeviceNet power supply, and must be grounded at that power supply in accordance with DeviceNet installation instructions. Switch Input Grounding The Switch Input circuits are functionally isolated from other circuits.
XM-940 Dynamic Measurement Terminal Base Mounting on the DIN Rail You can also mount the terminal base to a grounded mounting plate. Refer to the XM-124 Standard Dynamic Measurement Module User Manual, publication 1440-UM001. 1. Position the terminal base unit on the 35 x 7.5mm DIN rail (A) (Allen-Bradley pt no. 199-DR1 or 199-DR4) at a slight angle. Position terminal base at a slight angle and hook over the top of the DIN rail. 2.
XM-940 Dynamic Measurement Terminal Base 15 3. Hook the lip on the rear of the terminal base onto the top of the DIN rail, and rotate the terminal base onto the rail. 4. Press down on the terminal base unit to lock the terminal base on the DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base until flush with the DIN rail and release the locking tab to lock the base in place. 5.
XM-940 Dynamic Measurement Terminal Base Interconnecting Terminal Base Units Follow the steps below to install another terminal base unit. IMPORTANT Terminal base units are mounted left to right on the DIN rail. 1. Position the terminal base on the 35 x 7.5mm DIN rail (A). 2. Make certain the side connector (B) is fully retracted into the base unit. 3. Slide the terminal base unit over tight against the neighboring terminal base.
XM-940 Dynamic Measurement Terminal Base 17 Wiring IMPORTANT For more wiring connection information, refer to the XM-124 Standard Dynamic Measurement Module User Manual, publication 1440-UM001. Terminal Assignments WARNING ATTENTION If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
XM-940 Dynamic Measurement Terminal Base No. Description No.
XM-940 Dynamic Measurement Terminal Base 19 Specifications The following table lists the technical specifications for the XM-940 Dynamic Measurement Terminal Base Technical Specifications Attribute 1440-TB-A Backplane power 24V DC, 350 mA Class 2 / SELV Relay 120V AC, 50/60 Hz, 0.5 A resistive 110V DC, 0.3 A resistive 30V DC 1.5 A resistive Torque 0.8 N•m (7 lb•in) Conformal coating All printed circuit boards are conformally coated in accordance with IPC-A-610C Dimensions (WxDxH), approx 9.
XM-940 Dynamic Measurement Terminal Base Environmental Specifications Attribute 1440-TB-A Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry Heat) IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -20…65 °C (-4…149 °F) Maximum surrounding air temperature 65 °C (149 °F) Non-operating temperature EC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test BD, Operating Dry Heat) IED 60068-2-14 (Test Nb Operating Thermal Shock) -40…85 °C (-40…185 °F)
XM-940 Dynamic Measurement Terminal Base 21 Certifications Certification(1) 1440-TB-A c-UL-us Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support, you can find technical manuals, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://www.rockwellautomation.