Installation Instructions 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Catalog Numbers 1732E-IT4IM12R, 1732E-IR4IM12R Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic Discharge 3 Overview 4 Catalog Number Explanation 6 Install the Module 6 Set the Network Address 6 Mount the Module 8 Product Dimensions 8 Connect the I/O, Network and Auxiliary Cables to the Module 10 Configure the Module
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 3 Environment and Enclosure ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Additional Resources Resource Description 1732E ArmorBlock™ Dual-Port EtherNet/IP 4-Point Analog Modules Wiring Diagrams 1732E-WD003 Pinout guide wiring diagram for the ArmorBlock dual-port EtherNet/IP 4-Point Analog modules (1732E-IF4M12R, 1732E-OF4M12R, 1732E-IT4IM12R, 1732E-IR4IM12R).
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 5 Module Identification Function earth(1) EtherNet/IP D-code M12 connector EtherNet/IP D-code M12 connector Link 1 status indicator Link 2 status indicator Module status indicator Network status indicator Node address switches I/O status indicators M12 style I/O connectors Auxiliary power status indicator Micro-style power in Micro-style power out 45871 (1) Function Earth grounds the I/O block’s EtherNet/IP comm
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Optional Accessories The following table identifies optional accessories that you can use with the modules that have to be ordered separately. Option Catalog Number Snap-in individual marker card(1) 1492-MD6X9 Cold Junction Compensation Terminal Chamber (with embedded thermistor)(2) 871A-TS4CJC-DM or 871A-TR4CJC-DM (1) Provides labelling for the terminal blocks to allow for easy identification and description.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules • adjust the switches on the front of the module. • use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation BootP/DHCP. • retrieve the IP address from nonvolatile memory. 7 The I/O block reads the switches first to determine if the switches are set to a valid number. To set the network address: 1. Remove power. 2. Remove the switch dust caps. 3.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules If DHCP is not enabled, the I/O block uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory. Network Address Switch value 001 The module IP address cannot be the same as the gateway address. If the address switches are set to 001, the module IP address becomes 192.168.1.1, which is the same as the default gateway address. In this case, the module gateway address will be set to 0.0.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 9 Module Dimensions 37 (1.46) 16.2 (0.64) 19.8 (0.78) 166.5 (6.56) 179 (7.05) 168.6 (6.64) 27 (1.06) 6LGH 0RXQWLQJ 43.3 (1.70) Measurements are in millimeters (inches) 32 (1.26) 18 (0.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Mount the Module in High Vibration Areas If you mount the module in an area that is subject to shock or vibration, we recommend you use a flat and a lock washer to mount the module. Mount the flat and the lock washer as shown in the mounting illustration. Torque the mounting screws to 0.68 Nm (6 lb-in.).
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 11 Micro-style M12 5-Pin Input Female Connector – 1732E-IR4IM12R 3 2 5 1 4 45868 (View into connector) Pin 1 No Connect Pin 2 A Pin 3 B Pin 4 C Pin 5 No Connect A B C Ethernet Connector D-Code Micro Network Female Connector (View into connector 1) Pin 1 M12_Tx+ Pin 2 M12_Rx+ Pin 3 M12_Tx- Pin 4 M12_Rx- Pin 5 Connector shell shield GND 5 1 4 2 3 44808 IMPORTANT Use the 1585D–M4DC–H: Polyamide small body u
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules IMPORTANT Use two twisted pair CAT5E UTP or STP cables. D-Code M12 Pin Wire Color Signal 8-way Modular RJ45 Pin 1 White-orange TX+ 1 2 White-green RX+ 3 3 Orange TX- 2 4 Green RX- 6 ATTENTION: The device does not provide bonding or grounding terminal. Customer shall provide own bonding or grounding.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 13 Configure the Module Refer to the illustration for configuration operations.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Power Connectors Attach the micro-style 4-pin connector to the micro-style 4-pin receptacle as shown below. Micro-style 4-Pin Input Male Receptacle Male Input Female Output 2 1 3 4 (View into receptacle) Pin 1 Auxiliary power+ Pin 2 Module power+ Pin 3 Module power- Pin 4 Auxiliary power- 2 3 1 4 45764 45763 The power required by the module is based on a 4-pin micro-style connector system.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 15 Interpret LED Indicators This module has the following indicators: • Network, Module, and Link status indicators for EtherNet/IP • Auxiliary power status indicator • Individual I/O status indicators for inputs Status Indicators Link 1 status indicator Module status indicator Link 2 status indicator Network status indicator I/O status indicators Auxiliary power status indicator 45871 Publication 1732E-IN005B-
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Indicator Status for the Modules Indicator Status Module status Off No power applied to the device. Flashing red/green The module is performing POST (Power-On Self Test), which completes within 30 s. Green Device operating normally. Flashing red Module has experienced a recoverable fault. Possible minor faults include the following: • IP Address switches do not match configuration in use.
32E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 17 Indicator Status for the Modules Indicator Status Description I/O status Off The input channel is inactive, can be calibrated. Flashing Green Channel is calibrating. Green Normal operation, inputs being scanned. Flashing Yellow Thermistor fault. IMPORTANT Flashing Red Fault. Overrange, underrange, or process alarm is present. Red No power is detected.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules General Specifications Attributes Value Status indicators Module status – red/green Network status – red/green Link status – green/yellow Auxiliary power status – green I/O LED – red/green Dimensions, approx., HxWxD 179 x 37 x 27 mm (7.05 x 1.46 x 1.06 in.) Weight, approx. 0.34 kg (0.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 19 Input Specifications – 1732E-IT4IM12R Attributes Value Thermocouple types Type Material Temperature Range °C (°F) Voltage Range (mV) B Pt /30% Rh vs. Pt/5% Rh 40…1820 (104…3308) 0…13.820 C W/5% Re vs. W/26% Re 0…2320 (32…4208) 0…37.107 E Ni/Cr vs. Cu/Ni -270…1000 (-454…1832) -9.835…76.373 J Ni/Cr vs. Cu/Ni -210…1200 (-346…2192) -8.095…69.553 K Ni/Cr vs. Ni/Al -270…1372 (-454…2501.6) -6.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Input Specifications – 1732E-IT4IM12R Attributes Value Common mode rejection rate 120 dB @ 50/60 Hz Normal mode rejection rate 100 dB @ 50/60 Hz Sample Rate Filters(1) 50 Hz 60 Hz 250 Hz 500 Hz (1) Sample Rate/Notch Filter Frequency, selectable per channel.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 21 Input Specifications – 1732E-IR4IM12R Attributes Value Input range RTD type Temperature Range (°C) Voltage Range 100 Pt 385 0…390.48 -200…850 °C 0…156.25 mV 200 Pt 385 0…781 -200…850 °C 0…312.5 mV 100 Pt 3916 0…337.03 -200…630 °C 0…156.25 mV 200 Pt 3916 0…674.06 -200…630 °C 0…312.5 mV 10 Cu 427 0…19.116 -320…500 °C 0…19.53 mV 120 Ni 672 0…445.10 -70…445 °C 0…156.
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules Environmental Specifications Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…60 °C (-4…140 °F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 23 Certifications Certification (when product is marked)(1) Value c-UR-us UL Recognized Component Industrial Control Equipment, certified for US and Canada. See UL File E322657. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.