Installation Instruction POINT I/O 120/240V ac Expansion Power Supply Catalog Number 1734-EPAC Contents For See Page Important User Information 2 Before You Begin 4 Identify the Components 4 Install the ac Expansion Power Supply 6 Remove an ac Expansion Power Supply from the DIN Rail 6 Replace an ac Expansion Power Supply 7 Wire the ac Expansion Power Supply 8 North American Hazardous Location Approval 12 Specifications 13 Current Derating for DIN-Rail Mounting Orientation 16 Public
POINT I/O 120/240V ac Expansion Power Supply Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.literature.rockwellautomation.
POINT I/O 120/240V ac Expansion Power Supply 3 ATTENTION Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
POINT I/O 120/240V ac Expansion Power Supply ATTENTION Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • • • • • • Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment.
POINT I/O 120/240V ac Expansion Power Supply 5 DIN-rail Locking Screw C PA 4-E 173 RTB Removal Handle Removable Terminal Block (RTB) Module Label Interlocking Side Pieces 1734-EPAC Power Supply About the ac Expansion Power Supply The 1734-EPAC ac expansion power supply passes 120/240V ac field power to the I/O modules to the right of it.
POINT I/O 120/240V ac Expansion Power Supply You can use multiple ac expansion power supplies with POINT I/O adapters to assemble a full system. For instance, if you are using the 1734-ADN adapter, you may use an ac expansion power supply to add additional modules in 4 to 17 module increments. For example, if you had a 36 module system with a 1734 POINT I/O adapter, you would have two 1734-EPAC ac expansion power supplies to provide more PointBus current for modules to the right of the supply.
POINT I/O 120/240V ac Expansion Power Supply 7 WARNING When you connect or disconnect the removable terminal block (RTB) with field-side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. 2. Remove the module to the right of the power supply from its base unit. 3. Use a small-bladed screwdriver to rotate the DIN-rail locking screw to a vertical position.
POINT I/O 120/240V ac Expansion Power Supply Wire the ac Expansion Power Supply 1734-EPAC System Power Field Power NC NC PE PE L2/N L2/N NC = No Connection PE = Protective Earth Ground L2/N = Neutral L1 = 120/240V ac L1 L1 1734EPACfrt 120/240V ac Wiring WARNING If you connect or disconnect wiring while field side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
POINT I/O 120/240V ac Expansion Power Supply 9 0 1 NC NC 2 Connect ground wire to PE terminal. 3 PE This ac supply will be connected to the internal PE 4 5 L2/N L2/N L1 L1 V ac L1 = 120/240V ac, L2/N = Neutral PE = Protective Earth Ground 6 7 42513A Connect Terminal Terminals (For Continuing Power) L1 (120/240V ac) 6 7 L2/N (Neutral) 4 5 PE (Protective Earth Ground) 2 3 120/240V ac becomes the internal power bus for modules to the right.
POINT I/O 120/240V ac Expansion Power Supply Partitioning Examples Functional Adapter Status IB 2 1734-EPAC 1734-EPAC 1734-ADN DeviceNet Status IB 2 IM OW OX 2 2 2 IA OA OW 2 2 2 IB OB OB 4 2E 4E PointBus Status 1734-EPAC 1734-EPAC 1734-ADN System Power Field Power System Power Field Power System Power DeviceNet Power 0 1 0 1 0 12/24V dc Digital Supply 1 0 1 0 1 0 1 0 120V ac Supply 1 0 1 0 1 0 1 0 1 0 1 240V ac Supply 41970C Publication 1734-IN017A-EN-P - De
POINT I/O 120/240V ac Expansion Power Supply 11 Logical 1734-ADN Adapter Status DeviceNet Status PointBus Status 1734-EPAC IA OA OW 2 2 2 IE OE IB OB 2C 2 2 2E 1734-EPAC 1734-ADN System Power Field Power System Power DeviceNet Power 0 1 24V dc Supply 0 1 0 1 0 1 0 1 0 1 0 1 0 120V ac Supply 1 41970D Publication 1734-IN017A-EN-P - December 2005
POINT I/O 120/240V ac Expansion Power Supply North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, hazardous locations and nonhazardous locations only.
POINT I/O 120/240V ac Expansion Power Supply 13 Specifications Specifications - 120/240V ac Expansion Power Supply, Cat. No. 1734-EPAC I/O Module Capacity 12 modules typical (depending on current draw and orientation of modules; 4 to 17 based on module current requirements total not to exceed 1.3 A) (for example, 5 modules at 0.220 A; 17 modules at 0.075 A) Cat. No.
POINT I/O 120/240V ac Expansion Power Supply POINTBus Output Current Horizontal DIN rail mounting 1.3 A at 5.2V dc Vertical DIN rail mounting 1.0 A at 5.2V dc Input Overvoltage Protection MOV and fuse protected Interruption Output voltage will stay within specifications when input drops out for 10 ms at 85V ac with max load. Module Location Between I/O modules in 1734 system Breaks field power bus Limitations Use with POINT I/O adapters only Power Consumption 15.
POINT I/O 120/240V ac Expansion Power Supply 15 ESD Immunity IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges Radiated RF Immunity IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz 10V/m with 200 Hz 50% pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% pulse 100% AM at 1890 MHz EFT/B Immunity IEC 61000-4-4: ±4 kV at 5 kHz on power ports Surge Transient Immunity IEC 61000-4-5: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports Conducted RF Immunity IEC 61000-4-6: 10
Certifications (When Product is Marked)(2) CULUS CULUS CE C-Tick UL Listed Industrial Control Equipment, certified for US and Canada UL Listed for Class I, Division 2, Groups A, B, C and D Hazardous locations, certified for US and Canada European Union 89/336/EEC EMC Directive, compliant with: EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab.