Installation Instructions FLEX I/O DC Input, Output, and Input/Output Analog Modules Catalog Numbers 1794-IE12, 1794-OE12, and 1794-IE8XOE4 Table of Contents Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 3 North American Hazardous Location Approval 5 Install Your Analog Input/Output Module 6 Connect Wiring 6 Configuring Your Module 11 Data Table – 1794-IE12 11 Data Table – 1794-OE12 13 Data Table – 1794-IE8XOE4 14 Specifications 1
FLEX I/O DC Input, Output, and Input/Output Analog Modules Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.
FLEX I/O DC Input, Output, and Input/Output Analog Modules 3 Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11.
FLEX I/O DC Input, Output, and Input/Output Analog Modules WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. WARNING: If you connect or disconnect wiring while the field side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
FLEX I/O DC Input, Output, and Input/Output Analog Modules 5 North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, hazardous locations and nonhazardous locations only.
FLEX I/O DC Input, Output, and Input/Output Analog Modules Install Your Analog Input/Output Module 7 3 1 2 6 4 5 Description 45284 Description 1 Keyswitch 5 Groove 2 Terminal base 6 Alignment bar 3 FLEXBus connector 7 Latching mechanism 4 Module These modules mount on a 1794-TB3G or 1794-TB3GS terminal base. 1. Rotate the keyswitch (1) on the terminal base (2) clockwise to position 3 (1794-IE12), 4 (1794-OE12), or 5 (1794-IE8XOE4) as required. 2.
FLEX I/O DC Input, Output, and Input/Output Analog Modules 7 Connect Wiring Connect the wiring for the 1794-TB3G and 1794-TB3GS terminal bases as shown in the following figure: Terminal Base Wiring for the 1794-IE12/A Analog Input Module 0 1 2 3 I0 V0 I1 V1 4 5 6 7 8 I3 V3 I4 9 10 11 12 13 14 15 A 17 16 18 19 I2 V2 20 21 22 23 24 V4 I5 25 26 V5 27 I6 28 V6 29 I7 V7 30 31 32 33 B Chassis C0 C1 Ground 34 35 I8 V8 36 37 I9 38 V9 C2 C3 C4 C5 I10 V10 I11 V11 C6 C7
FLEX I/O DC Input, Output, and Input/Output Analog Modules Wire Connections for the 1794-IE12/A Analog Input Module Channel Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 Input 9 Input 10 Input 11 -V DC Common +V DC Power Chassis Ground (Shield) Signal Type Label Marking 1794-TB3G or 1794-TB3GS Input Common Terminal Current I0 A-0 B-17 Voltage V0 A-1 Current I1 A-2 B-18 Voltage V1 A-3 Current I2 A-4 B-23 Voltage V2 A-5 Current I3 A-6 B-24 Voltage V3 A-7 Current I4 A-8 B-25 Volt
FLEX I/O DC Input, Output, and Input/Output Analog Modules 9 Wire Connections for the 1794-OE12/A Analog Output Module Channel Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Output 9 Output 10 Output 11 -V DC Common +V DC Power Chassis Ground (Shield) Signal Type Label Marking 1794-TB3G or 1794-TB3GS Output Common Terminal Current I0 A-0 B-17 Voltage V0 A-1 Current I1 A-2 B-18 Voltage V1 A-3 Current I2 A-4 B-23 Voltage V2 A-5 Current I3 A-6 B-24 Voltage V3 A-7 Current
FLEX I/O DC Input, Output, and Input/Output Analog Modules Wire Connections for the 1794-IE8XOE4/A Analog 8 Input/4 Output Module Channel Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Output 9 Output 10 Output 11 -V DC Common +V DC Power Chassis Ground (Shield) Signal Type Label Marking 1794-TB3G or 1794-TB3GS Output Common Terminal Current I0 A-0 B-17 Voltage V0 A-1 Current I1 A-2 B-18 Voltage V1 A-3 Current I2 A-4 B-23 Voltage V2 A-5 Current I3 A-6 B-24 Voltage V3
FLEX I/O DC Input, Output, and Input/Output Analog Modules 11 Configuring Your Module You configure your output/input module by setting bits in the configuration word. Data Table – 1794-IE12 Dec. Oct.
FLEX I/O DC Input, Output, and Input/Output Analog Modules Range Selection Bits for the 1794-IE12, 1794-OE12, and 1794-IE8XOE4 Range -10...+10V DC 4...20 mA Out of Range < -10.0V or > 10.0V < 4.0mA or > 20.0 mA 0...20 mA < 0.0 mA or > 20.0 mA (1) Range Setting Set bits for each channel pair 00 = off 01 = 0...20 mA 10 = 4...
FLEX I/O DC Input, Output, and Input/Output Analog Modules 13 Data Table – 1794-OE12 Dec. 15 14 13 12 11 10 9 8 7 6 Oct.
FLEX I/O DC Input, Output, and Input/Output Analog Modules Data Table – 1794-IE8XOE4 Dec. Oct.
FLEX I/O DC Input, Output, and Input/Output Analog Modules 15 Specifications General Specifications for the 1794-IE12, 1794-OE12, and 1794-IE8XOE4 Modules Attribute 1794-IE12 Indicators 1 red/green power/status indicator 1794-OE12 Recommended terminal base 1794-TB3G or 1794-TB3GS FLEXBus current 80 mA 1794-IE8XOE4 Power supply Voltage, nom.(nom) Specification 24V DC (2) Certification 24V DC Voltage, range 10.5...31.2V DC 24V DC (2) 24V DC 10.0...31.2V DC 24V DC (2) 24V DC 10.0...31.
FLEX I/O DC Input, Output, and Input/Output Analog Modules Environmental Specifications Attribute 1794-IE12 1794-OE12 1794-IE8XOE4 Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20...60 °C (-4...
FLEX I/O DC Input, Output, and Input/Output Analog Modules 17 Output Specifications – 1794-OE12 and 1794-IE8XOE4 Modules Attribute 1794-OE12 Number of outputs 12 single-ended, nonisolated 4 single-ended, nonisolated Output voltage terminal 0V output until module is configured +10V (user configurable) Output current terminal 0 mA output until module is configured 4...20 mA (user configurable) 0...20 mA (user configurable) Output resolution Voltage terminal Current terminal 16 bit 320 μV/cnt 0.
FLEX I/O DC Input, Output, and Input/Output Analog Modules Input Specifications – 1794-IE12 and 1794-IE8XOE4 Modules Attribute 1794-IE12 Input voltage terminal +10V (user configurable) Input current terminal Specification Certification 4...20 mA (user configurable) 0...20 mA (user configurable) Input impedance, nom. (nom) Voltage terminal Current terminal > 1 MΩ < 100 Ω (2) Normal mode rejection ratio 1794-IE8XOE4 Voltage/current terminal: -3 dB @ 0.
FLEX I/O DC Input, Output, and Input/Output Analog Modules 19 Certifications (when product is marked)(1) Attribute Value c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.