Manual

ICS Regent+Plus
®
PD
-
7016
Industrial Control Services
1
AC Digital Output Module
110 VAC
(T7444)
Issue 1,
March, 06
The AC digital output module provides control of 16 user
output loads. One type of module is available to interface to
outputs powered from a nominal 110 VAC field power su
pply.
Each module's triplicated I/O Safetybus interface ensures that
no Regent system failure can incorrectly apply power to an
output, and that no failure in the module can affect the
operation of the Regent system or other I/O modules in the
system.
Features
·
Sixteen output circuits, configured as two isolated groups of
eight circuits each.
·
Hot
-
replaceable.
·
Automatic self
-
testing of triplicated I/O Safetybus circuits and
many simplex logic circuits.
·
2 amp output circuits.
·
Zero
-
cross load switching.
·
Individual front panel indicators on each module show active
and fault, shutdown, blown fuse, and output on/off status (logic
side).
·
2500 volt minimum electrical isolation between field and logic
circuits.
·
Fuses accessible from front panel.
·
TÜV certified, Risk Class 5, non
-
interfering.