Technical data

Manual
Double Sheet Detector R1000 series E20
Start-up
B0046991 / Rev. 1.6
110
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
System parameter 4: Adjusting the measuring mode.
Fig.. 57: Adjusting the measuring mode
Possible measurement modes:
External continuous measurement:
The system executes measurements, as long as the “Measurement start“ signal is applied
via the external PLC input. The repetition rate of the measurement depends on the type of
sensor: 0.5 seconds for P42, P30, P42A, P75V; 1 second for P36; 2 seconds for P75.
External single measuring:
The system measures once if the “Measurement start“ signal is applied via the external PLC
input. Each measurement must initiated separately. The hints in chapter 6.1.4.1 „timing
diagram single measurement“ must be abided by.
Demo mode:
This mode of operation is intended for equipment demonstrations, but not for normal process
operation. The system executes measurements continuously. The repetition rate of the
measurement depends on the type of sensor: 1 second for P42, P30, P42A, P75V;
2 seconds for P36; 4 seconds for P75.
System parameter 5: Adjusting the baud rate of the serial RS232 interface (for C version only).
Fig.. 58: Adjusting the baud rate
According to the requirements of the super-ordinated system, values from 300 – 19200 can be set.
System parameter 6: Deleting all measuring programs.
Fig.. 59: Deleting of measuring programs
Attention The deletion cannot be undone.
system param. 4
mode: ext.cont.
system param. 5
baud rate: 9600
system param. 6
CLR param.: no