Reference Manual
Table Of Contents
- Rosemount 1408H Level Transmitter
- Contents
- 1 Introduction
- 2 Transmitter overview
- 3 Mechanical installation
- 3.1 Safety messages
- 3.2 Installation considerations
- 3.3 Mounting preparations
- 3.4 Mount transmitter on tank
- 4 Electrical installation
- 5 Configuration
- 6 Operation and maintenance
- 7 Service and troubleshooting
- 7.1 Safety messages
- 7.2 Diagnostic messages
- 7.2.1 Device hardware fault – Device exchange
- 7.2.2 General power supply fault – Check availability
- 7.2.3 Device software fault – Check firmware revision
- 7.2.4 Parameter error – Check data sheet and values
- 7.2.5 Short circuit – Check installation
- 7.2.6 Device memory failure – Restore default settings
- 7.2.7 Level measurement lost – Check application
- 7.2.8 Simulation active – Check operational mode
- 7.2.9 Device temperature over-run – Clear source of heat
- 7.2.10 Device temperature under-run – Insulate device
- 7.2.11 Primary supply voltage over-run – Check tolerance
- 7.2.12 Primary supply voltage under-run – Check tolerance
- 7.2.13 Maintenance required - Cleaning
- 7.3 Troubleshooting incorrect level readings
- 7.3.1 Reported level is too high or low
- 7.3.2 Level is stuck in measuring range
- 7.3.3 Level is stuck in full tank
- 7.3.4 Level value drops when close to antenna
- 7.3.5 Measured level fluctuates
- 7.3.6 Measured level is occasionally unstable
- 7.3.7 Lagging of measured level
- 7.3.8 Incorrect level at 100% (20 mA)
- 7.3.9 Incorrect level when product surface is above 50%
- 7.3.10 Dropping of level close to tank bottom
- 7.3.11 Level measurement is lost in an empty tank
- 7.3.12 Alarm mode close to tank bottom
- 7.4 Managing disturbance echoes
- 7.5 Service and troubleshooting tools
- 7.6 Service support
- A Specifications and reference data
- A.1 Performance specifications
- A.2 Functional specifications
- A.3 Physical specifications
- A.4 Dimensional drawings
- B Product certifications
- C Configuration parameters
5.3.3 FDT
®
/DTM framework
Download the IODD file
Procedure
Download the IODD from the IODDFinder portal at Ioddfinder.io-link.com.
Integrate IODDs into an FDT
®
/DTM framework
An IODD DTM Interpreter is required to integrate IODDs into an FDT/DTM environment
(e.g PACTware).
Prerequisites
The IODD DTM Interpreter is usually included in the FDT/DTM software installation
package.
Procedure
1. Start the
IODD DTM Interpreter software.
2. Select Add IODD.
3. Browse to the IODD file and select Open.
4. Start the configuration tool and update the device catalog.
Need help?
If the new DTM is not added automatically at start-up, then select
View → Device
Catalog → Update Device Catalog.
Reference Manual Configuration
00809-0100-4480 September 2020
Reference Manual 37