5.5.2 Enter the reference height
Procedure
1. Under
Menu, select Parameter Basic Setup.
2. Enter the Reference Height.
3. Select Write to device.
Related information
Reference height
5.5.3 Configure the analog output
The transmitter can be set to output the level as a 4-20 mA signal.
Procedure
1.
Under
Menu, select Parameter Basic Setup.
2. In the OUT2 Configuration list, select Analog Output 4-20 mA.
3. In the Alarm Mode list, select Low Alarm or High Alarm.
4. Select OUT2 Analog Output 2.
5. Enter the desired Upper Range Value (20 mA).
6. Enter the desired Lower Range Value (4 mA).
7. Select Write to device.
Related information
Analog output
5.5.4 Configure the digital output
The transmitter can be set to output a switching signal for high and low level limits (using
the same pin).
Procedure
1.
Under
Menu, select Parameter Basic Setup.
2. In the OUT1 Configuration or OUT2 Configuration list, select Digital Output Normally
Open.
3. In the Digital Outputs P-n list, select PnP or nPn.
4. Select Digital Output 1 or Digital Output 2.
5. Set the alarm parameters as desired.
6. Select Write to device.
Related information
Digital output
Reference Manual Configuration