Reference Manual
Table Of Contents
- Rosemount 1408H Level Transmitter
- Contents
- 1 Introduction
- 2 Transmitter overview
- 3 Mechanical installation
- 3.1 Safety messages
- 3.2 Installation considerations
- 3.3 Mounting preparations
- 3.4 Mount transmitter on tank
- 4 Electrical installation
- 5 Configuration
- 6 Operation and maintenance
- 7 Service and troubleshooting
- 7.1 Safety messages
- 7.2 Diagnostic messages
- 7.2.1 Device hardware fault – Device exchange
- 7.2.2 General power supply fault – Check availability
- 7.2.3 Device software fault – Check firmware revision
- 7.2.4 Parameter error – Check data sheet and values
- 7.2.5 Short circuit – Check installation
- 7.2.6 Device memory failure – Restore default settings
- 7.2.7 Level measurement lost – Check application
- 7.2.8 Simulation active – Check operational mode
- 7.2.9 Device temperature over-run – Clear source of heat
- 7.2.10 Device temperature under-run – Insulate device
- 7.2.11 Primary supply voltage over-run – Check tolerance
- 7.2.12 Primary supply voltage under-run – Check tolerance
- 7.2.13 Maintenance required - Cleaning
- 7.3 Troubleshooting incorrect level readings
- 7.3.1 Reported level is too high or low
- 7.3.2 Level is stuck in measuring range
- 7.3.3 Level is stuck in full tank
- 7.3.4 Level value drops when close to antenna
- 7.3.5 Measured level fluctuates
- 7.3.6 Measured level is occasionally unstable
- 7.3.7 Lagging of measured level
- 7.3.8 Incorrect level at 100% (20 mA)
- 7.3.9 Incorrect level when product surface is above 50%
- 7.3.10 Dropping of level close to tank bottom
- 7.3.11 Level measurement is lost in an empty tank
- 7.3.12 Alarm mode close to tank bottom
- 7.4 Managing disturbance echoes
- 7.5 Service and troubleshooting tools
- 7.6 Service support
- A Specifications and reference data
- A.1 Performance specifications
- A.2 Functional specifications
- A.3 Physical specifications
- A.4 Dimensional drawings
- B Product certifications
- C Configuration parameters
3. If the condition persists, replace the device.
Related information
Perform a device reset
Restore to factory settings
7.2.4 Parameter error – Check data sheet and values
Alarm classification
Device status
Functional Check
Class
Error
Possible cause
The device has detected a configuration error.
Recommended actions
1. If analog output is used, check Upper and Lower Range Values.
2.
If digital output is used, check High and Low Alarm Set Points.
3. If condition persists, restore default settings and reconfigure the device.
Related information
Upper/lower range value
Alarm set points
Restore to factory settings
7.2.5 Short circuit – Check installation
Alarm classification
Device status
Functional Check
Class
Error
Possible cause
Short circuit on the digital output.
Recommended actions
Check cable and connections.
Reference Manual Service and troubleshooting
00809-0100-4480 September 2020