3. If the condition persists, replace the device.
Related information
Perform a device reset
Restore to factory settings
7.2.4 Parameter error – Check data sheet and values
Alarm classification
Device status
Functional Check
Class
Error
Possible cause
The device has detected a configuration error.
Recommended actions
1. If analog output is used, check Upper and Lower Range Values.
2.
If digital output is used, check High and Low Alarm Set Points.
3. If condition persists, restore default settings and reconfigure the device.
Related information
Upper/lower range value
Alarm set points
Restore to factory settings
7.2.5 Short circuit – Check installation
Alarm classification
Device status
Functional Check
Class
Error
Possible cause
Short circuit on the digital output.
Recommended actions
Check cable and connections.