Reference Manual

Table Of Contents
7.2.6 Device memory failure – Restore default settings
Alarm classification
Device status
Functional Check
Class
Error
Possible cause
Configuration data has been corrupted, for example, due to a power loss during writing.
Recommended actions
1. Restore default settings, restart device, and reconfigure the device.
2.
If the condition persists, replace the device.
Related information
Restore to factory settings
Perform a device reset
7.2.7 Level measurement lost – Check application
Alarm classification
Device status
Functional Check
Class
Error
Possible cause
No valid level reading. Reasons may be multiple:
No valid surface echo peak in the measuring range
Incorrect device configuration
Recommended actions
1. Analyze the Echo Peaks and check device configuration, especially General
Threshold.
2. Check device physical installation (for instance antenna contamination).
3. Consider increasing Measurement Recovery Time parameter for intermittent
conditions.
4. Restore default settings, restart device, and reconfigure the device.
5. If the condition persists, replace the device.
Related information
Analyze the echo peaks
Adjust the general threshold
Measurement recovery time
Restore to factory settings
Service and troubleshooting Reference Manual
September 2020 00809-0100-4480
48 Rosemount 1408H Level Transmitter