Reference Manual

Table Of Contents
7.3 Troubleshooting incorrect level readings
7.3.1 Reported level is too high or low
Figure 7-1: Symptom
A
B
C
D
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Incorrect tank geometry configuration.
Recommended actions
Verify the tank geometry parameters are configured correctly (especially the
Reference Height).
Analyze the Echo Peaks and check General Threshold.
Restore default settings and reconfigure the device.
Related information
Reference height
Analyze the echo peaks
Adjust the general threshold
Restore to factory settings
Service and troubleshooting Reference Manual
September 2020 00809-0100-4480
52 Rosemount 1408H Level Transmitter