7.3.4 Level value drops when close to antenna
Level value drops to a lower value when product surface is close to antenna.
Figure 7-4: Symptom
A
B
C
D
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Product surface is within the Upper Null Zone and a disturbance echo is interpreted as the
product surface.
Recommended actions
Check the setting of the Upper Null Zone.
Related information
Change the upper null zone
Reference Manual Service and troubleshooting