7.3.12 Alarm mode close to tank bottom
Symptom
When the product surface is near the sloped tank bottom, the transmitter enters alarm
mode.
Figure 7-12: Symptom
A
B
C
D
A. Level
B. Time
C.
Actual level
D. Reported level
Possible cause
Reduction of projected surface area close to sloping tank bottom.
Recommended actions
Verify the tank geometry parameters are configured correctly (especially the
Reference Height and Bottom Offset).
Related information
Reference height
Bottom offset
7.4 Managing disturbance echoes
There are two general methods for managing disturbance echoes:
Set general threshold to filter out weak disturbance echoes and noise.
Increase the Upper Null Zone to block out disturbance echoes at the top of the tank.
Reference Manual Service and troubleshooting