Table 7-1: Echo Peak Types
Type Description
Surface Echo tracked as the current surface echo
Unknown Echo identified as unknown (can be a surface candidate)
Suppressed Echoes that are identified but suppressed by the device
Tank bottom echo Echo considered as an echo from the tank bottom
7.5.2 Perform a device reset
The function is used to reset/restart the electronics without re-cycling the power.
Procedure
1. Under
Menu, select Parameter Service Tools Maintenance.
2. Select Device Reset.
7.5.3 Restore to factory settings
This function restores the transmitter to factory settings (user configuration is
overwritten).
Procedure
1.
Under
Menu, select Parameter Service Tools Maintenance.
2. Select Restore Factory Settings.
7.5.4 Use the simulation mode
It is possible to set the level to a simulated value for testing purposes. The simulated value
affects both digital and analog output.
Procedure
1.
Under
Menu, select Parameter Service Tools Simulation.
2. In the Simulated Level box, enter the desired value.
3. Select Write to device.
4. Select Start simulation (60 min).
7.5.5 Calibrate analog out
Use this function to calibrate the analog output by comparing the actual output current
with the nominal 4 mA and 20 mA currents. Calibration is done at factory and the analog
output does not normally need to be recalibrated.
Prerequisites
Connect a calibrated ampere meter to the analog output loop.
Service and troubleshooting Reference Manual
September 2020
00809-0100-4480
66 Rosemount 1408H Level Transmitter