C.2 Basic setup
C.2.1 Engineering units
Sets the unit of measure for length and temperature.
Option Length unit Temperature unit
Metric m °C
Imperial inch °F
After appropriate units have been selected, all configuration parameters and transmitter
variables will be expressed in these units.
C.2.2 Reference height
Distance between the Device Reference Point and Zero Level.
Figure C-2: Reference Height
A
B
C
A. Device Reference Point
B. Reference Height
C. Zero Level
Ensure the Reference Height is set as accurate as possible. The transmitter measures the
distance to the product surface and subtracts this value from the Reference Height to
determine the level.