C.2.6 Write protection
The transmitter can be software write protected to prevent unauthorized configuration
changes.
C.3 Digital output
C.3.1 Alarm configuration
High alarm
Enable or disable the high level alarm (overfill alarm).
Figure C-4: Example - High Alarm
A
B
C
D
O
f
f
On
A. Level
B. Time
C.
SP1 - High alarm set point
D. SP1 - Hysteresis high alarm
Low alarm
Enable or disable the low level alarm (dry run alarm).
Figure C-5: Example - Low Alarm
A
B
C
D
O
f
f
On
A. Level
B.
Time
C.
SP2 - Hysteresis low alarm
D. SP2 - Low alarm set point
Configuration parameters Reference Manual
September 2020 00809-0100-4480
88 Rosemount 1408H Level Transmitter