Reference Manual

Table Of Contents
C.4 Analog output
C.4.1 Upper/lower range value
Enter the range values that correspond to the analog output values 4 and 20 mA. In
normal operation, the transmitter will drive the output in response to level from the lower
to upper saturation points.
Note
The 20 mA point should be set below the reduced accuracy zone at the top of the tank.
Figure C-8: Example of Range Value Settings
B
E
C
D
A
A. Reduced accuracy zone
B. 100% (20 mA)
C.
Zero Level
D. Level measurement range 0-100%
E. 0% (4 mA)
Related information
Accuracy over measuring range
C.4.2 Alarm mode
The transmitter automatically and continuously performs self-diagnostic routines. If a
failure or a measurement error is detected, the transmitter drives the output to selected
alarm limit (high or low).
Reference Manual Configuration parameters
00809-0100-4480
September 2020
Reference Manual 91